On-off, Spring Return Fail-Safe, 24 V
Wiring Diagrams
TLF24 (-S) Typical Specification
On-off spring return damper actuators shall be direct
coupled type which require no crankarm and linkage and be
capable of direct mounting to a shaft up to a 3/4” diameter
and center a 1/2” shaft. The actuators must be designed
so that they may be used for either clockwise or
counterclockwise fail-safe operation. Actuators shall be
protected from overload at all angles of rotation. If required,
one SPDT auxiliary switch shall be provided having the
capability of being adjustable. Actuators with auxiliary
switch must be constructed to meet the requirements for
double insulation so an electrical ground is not required to
meet agency listings. Actuators are UL listed and CSA
certified and be manufactured under ISO 9001 International
Quality Control Standards. Actuators shall be as
manufactured by Belimo.
1 Common
2 + Hot
2
24 VAC Transformer
TLF24
Line
Volts
3
5
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
1 Common
2 + Hot
2
24 VAC Transformer
TLF24-S
Line
Volts
3
S1
S2
S3
NC
NO
0° to 95°
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
On-off wiring for TLF24
On-off wiring for TLF24-S
W458
W459
CAUTION
INSTALLATION NOTES
2
Equipment damage!
Actuators may be connected in parallel.
Power consumption must be observed and input
impedance must be observed.
3
5
Actuator may also be powered by 24 VDC.
Actuators with plenum rated cable do not have
numbers on wires; use color codes instead.
Actuators with appliance cables use numbers.
APPLICATION NOTES
Meets cULus or UL and CSA requirements without
the need of an electrical ground connection.
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Page 166: ...Notes Work Pad 166 I20683 Subject to change...