15
I20683 - Subject to change.
TAF
TAF24 (-S)
On-off, Spring Return Fail-Safe, 24 V
Wiring Diagrams
TAF24 (-S) Typical Specification
On-off spring return damper actuators shall be direct coupled
type which require no crankarm and linkage and be capable
of direct mounting to a jackshaft up to a 1.05” diameter. The
actuators must be designed so that they may be used for
either clockwise or counterclockwise fail-safe operation.
Actuators shall have a manual positioning mechanism
accessible on its cover. Actuators shall use a brushless DC
motor and be protected from overload at all angles of rotation.
Run time shall be constant and independent of torque. If
required, 2 SPDT auxiliary switches shall be provided with
one switch having the capability of being adjustable. Actuators
with switches must be constructed to meet the requirement for
double insulation so an electrical ground connection is not
required to meet agency listings. Actuators are UL listed and
CSA certified, and be manufactured under ISO 9001
International Quality Control Standards. Actuators shall be
as manufactured by Belimo.
1 Common
2 + Hot
2
24 VAC Transformer
TAF24
Line
Volts
3
5
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
orother individual who has beenproperly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
On-off wiring for TAF24
W450
1 Common
2 + Hot
2
24 VAC Transformer
TAF24-S
Line
Volts
3
S1
S2
S3
S4
S5
S6
NC
NO
NC
NO
5°
25° to 85°
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
orother individual who has beenproperly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
On-off wiring for TAF24-S
W451
CAUTION
INSTALLATION NOTES
2
3
5
Actuator may also be powered by 24 VDC.
Actuators with plenum rated cable do not have
numbers on wires; use color codes instead.
Actuators with appliance cables use numbers.
APPLICATION NOTES
Meets cULus or UL and CSA requirements without
the need of an electrical ground connection.
Equipment damage!
Actuators may be connected in parallel. Power con-
sumption and input impedance must be observed.
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Page 166: ...Notes Work Pad 166 I20683 Subject to change...