108
I20683 - Subject to change.
Auxiliary Switches S1A GR, S2A GR
For the Non-Spring Return Direct-Coupled Actuators
Wiring Diagrams
S2A GR
●
●
●
●
●
●
S1
S2
S3
S4
S5
S6
S1A GR
●
●
●
NC
NO
S1
S2
S3
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Types
S1A GR
1 SPDT
3 ft, 18 GA Appliance Cable
S1A/300 GR
1 SPDT
6 ft, 18 GA Appliance Cable
S1A/500 GR
1 SPDT
10 ft, 18 GA Appliance Cable
S2A GR
2 SPDT
3 ft, 18 GA Appliance Cable
S2A/300 GR
2 SPDT
6 ft, 18 GA Appliance Cable
S2A/500 GR
2 SPDT
10 ft, 18 GA Appliance Cable
Technical Data
S1A GR
S2A GR
Number of Switches
1 SPDT
2 SPDT
Switching Capacity
3A (0.5A), 250 VAC
Switching Point
Adjustable over Full Rotation
(0° to 95°).
Pre-Setting with Scale Possible.
Humidity
5 to 95% RH non-condensing
Ambient Temperature -22°F to +122°F [-30°C to +50°C]
Storage Temperature -40°F to +176°F [-40°C to +80°C]
Housing
NEMA 2 / IP54
Housing Rating
UL94-5VA
Servicing
Maintenance Free
Agency Listings
cULus acc. to UL 60730-1/-2-14 and
CAN/CSA C22.2 No.24 CE according
to 73 / 23 / EEC
Quality Standard
ISO 9001
Weight
4.6 oz [130 g]
6.0 oz [170 g]
Application
The S1A GR and S2A GR auxiliary switches are used to
indicate when a desired position of a damper is reached or to
interface additional controls for a specific control sequence.
Operation
The S1A GR and S2A GR auxiliary switches are mounted
onto the direct coupled actuator. The switches are modular
units that mount directly onto TLM, TNM, TAM, and TGM type
actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator clamp and offers
direct transmission of the actuator position to the micro switch
cams. The switching points can be set over the full scale of
0 to 1 simply by adjusting the slotted discs.
Mounting Instructions
1. Remove position indicator from actuator.
2. Press down the manual override button and rotate the
actuator fully counter-clockwise.
3. Turn the driver disk on the switch fully counterclockwise.
4. Slide switch onto the actuator using the actuator guiding
grooves on the sides of the actuator.
5. Check for correct mating of the driver disk to the
universal clamp.
6. Adjust switch dials as necessary.
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Page 166: ...Notes Work Pad 166 I20683 Subject to change...