162
I20683 - Subject to change.
Applications
V-A. (continued) Wiring for Multiple Actuators on One Shaft (TAF/TGM, for other actuators use next higher torque actuator)
●
24 VAC Transformer
Note:
See table on page 161
for maximum number of
actuators allowed.
Line
Volts
(–)
(+)
Control Signal
1
2
3
5
1
2
3
5
1
2
3
5
1
2
3
5
All actuators except TAF24-SR
●
24 VAC Transformer
Note:
TAF24-SR must be wired in this
manner when more than one actua-
tor is mounted on a single shaft.
A maximum of 4 actuators may be
mounted to a single shaft.
Line
Volts
(–)
(+)
Control Signal
1
2
3
5
1
2
3
5
1
2
3
5
1
2
3
5
TAF24-SR
●
●
24 VAC Transformer
DAMPER 1
DAMPER 2
24 VAC Transformer
Note:
Shown with typical 2 transformer wiring, if one transformer
does not have enough capacity for 6 actuators.
Line
Volts
Line
Volts
(–)
(+)
Control Signal
1
2
3
5
1
2
3
5
1
2
3
5
1
2
3
5
1
2
3
5
1
2
3
5
Typical wiring of multiple dampers with more than one TAF24-SR mounted on a single shaft.
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Page 166: ...Notes Work Pad 166 I20683 Subject to change...