I20683 - Subject to change.
Torque min. 60 in-lb, for control of air dampers
Application
For on-off, fail-safe control of dampers in HVAC systems.
Actuator sizing should be done in accordance with the damper
manufacturer’s specifications. Control is on-off from an
auxiliary contact, or a manual switch.
The actuator is mounted directly to a damper shaft up to 1.05”
in diameter by means of its universal clamp. A crank arm and
several mounting brackets are available for applications where
the actuator cannot be direct coupled to the damper shaft.
Operation
The TNF series actuators provide true spring return operation
for reliable fail-safe application and positive close off on air tight
dampers. The spring return system provides constant torque to
the damper with, and without, power applied to the actuator.
The TNF series provides 95° of rotation and is provided with a
graduated position indicator showing 0° to 95°.
The actuator may be stalled anywhere in its normal rotation
without the need of mechanical end switches.
The TNF24-S version is provided with one built in auxiliary
switch. This SPDT switch is provided for safety interfacing or
signaling, for example, for fan start-up. The switching function
is adjustable between 5° and 85°.
For all accessories, see pages 110 and 132.
TNF24 (-S)
On-off, Spring Return Fail-Safe, 24 V
Technical Data
TNF24 (-S)
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption
running: 5 W; holding: 2.6 W
Transformer sizing
8 VA (class 2 power source)
Electrical connection
3 ft, 18 GA appliance cable
1/2” conduit connector
Overload protection
Electronic throughout 0° to 95° rotation
Electrical protection
Auxiliary switches are double insulated
Angle of rotation
95°, adjustable 30 to 95° w/ accessories
Torque
60 in-lb [7 Nm] constant torque
Direction of rotation
reversible with CW/CCW mounting.
Position indication
visual indicator, 0° to 95° (0° is spring
return position)
Auxiliary switches
1 x SPDT 7A (2.5A) @ 250 VAC, UL listed
adjustable 5° to 85°
Running time
motor: < 75 sec
spring: < 60 sec
Humidity
5 to 95% RH non-condensing
Ambient temperature
-22°F to +122°F [-30°C to +50°C]
Storage temperature
-40°F to +176°F [-40°C to +80°C]
Housing
NEMA type 2 / IP54
Housing material
zinc coated steel
Agency listings
UL 873 listed, CSA C22.2 No.24 certified
Noise level
max. 45 dB (A)
Servicing
maintenance free
Quality standard
ISO 9001
Weight
6.6 lbs (3.0 kg.)
(TNF24-S)
(nominal)
1.97"
3.15" [80]
3.86" [98]
2.24"
[57]
[50]
1.93"
[49]
2.64"
[67]
0.26" [6.5]
5.85" [148.5]
10.59" [269]
0.35" [9]
0.39" [10]
0.65" [16.5]
0.19" [5]
K4-2 US (supplied)
1/2" Centered
(Default)
3/4"
Centered
(Field
Selectable)
1.05"
Centered
(Field
Selectable)
K4-1 US (optional)
3/4" to 1.05"
Adjustable
K4 US (optional)
3/8"
to
3/4"
Adjustable
3.25" [82.7]
Dimensions
[All numbers in brackets are in millimeters.]
LISTED
94D5
TEMP. IND &
REG. EQUIP
.
UL
D011
30
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Page 166: ...Notes Work Pad 166 I20683 Subject to change...