161
I20683 - Subject to change.
Wiring Guide
Applications
V. Application Information
V-A. Wiring for Multiple Actuators on One Shaft (TAF/TGM, for other actuators use next higher torque actuator)
Actuators which may be
used on one shaft:
Max
Quantity
Model
Per Shaft
TAF24(-S)
4
TAF24-SR
4
TGM24-SR
2
TAM24-SR
4
1
24 VAC Transformer
Line
Volts
1
Common
2
+ Hot
TAF24
1
Common, Neutral
2
+ Hot
TAF24
3
3
●
●
●
● ●
●
1
1
Neutral
2
Hot
TAF120
TAF120
1
Common, Neutral
2
+ Hot
●
●
●
● ●
●
L1 N
L2 H
2
3
4
1
Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption
must be observed.
May also be powered by 24 VDC.
Set reversing switch (CCW-CW)(A-B) as required by control
logic and control range.
Notes:
●
24 VAC Transformer
Line
Volts
1
Common
2
+ Hot
3
Y
1
Input, 0 to 10 V
4
Y
2
5
U
(–)
(+)
Control Signal
0 to 10 VDC
4
1
●
●
●
●
●
●
1
Common
2
+ Hot
3
Y
1
Input, 0 to 10 V
4
Y
2
5
U
4
A
B
A
B
TGM24-SR
TAM24-SR
TGM24-SR
TAM24-SR
●
●
24 VAC Transformer
Line
Volts
1
Common
2
+
3
+
4
2
1
TGM24
TAM24
●
●
●
●
●
●
●
1
Common
2
+
3
+
4
A
B
A
B
TGM24
TAM24
●
24 VAC Transformer
Line
Volts
1
Common
2
+ Hot
3
Y
1
Input, 0 to 10 V
4
Y
2
5
U Output 2 to 10 V
(–)
(+)
Control Signal
2 to 10 VDC
4
5
1
TAF24-SR
TAF24-SR
●
●
●
●
●
1
Common
2
+ Hot
3
Y
1
Input, 0 to 10 V
4
Y
2
5
U
4
CCW CW
CCW CW
To Other
Actuators
To Other Actuators
To Other Actuators
To Other Actuators
(TAMB24 (-S) only)
To Other Actuators
(TAMB24-SR only)
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...
Page 166: ...Notes Work Pad 166 I20683 Subject to change...