Application
The PS-100 power supply and signal simulator is designed to
operate most proportional, floating, and on-off style actuators
without the presence of a controller.
The PS-100 can produce 24 VAC on-off and floating control
signal along with a 0 to 10 VDC and 135
Ω
proportional sig-
nal. A multi-function digital display is provided which can read
either the 0 to 10 VDC output or a 0 to 10 VDC feedback
signal either as voltage or percentage of control.
The PS-100 comes with a 120 to 24 VAC, plug into the wall
transformer for power. Both the PS-100 and transformer are
supplied in a black fabric carrying case.
Replacement Power Supply: PS-XFMR
3.75"
[9.5]
2" [5]
6.25"
[16]
2.75"
[7]
Power Supply, Signal Simulator PS-100
Technical Data
PS-100
Power supply
120 VAC 50/60 Hz
Power consumption
< 4 W without actuator
Transformer
Primary: 120 VAC, 35 W
Secondary: 24 VAC, Class 2 trans.
PN: PS-XFMR
Terminal outputs
Push-button, wire terminals (12)
On-off, Floating Point
135
Ω
, 0 to 10 VDC
Input
0 to 10 VDC
Display
LCD
Readouts, Output
0 to 10 VDC in volts or percentage
based on a 2 to 10 VDC control span
Readouts, Input
0 to 10 VDC in volts or percentage
based on a 2 to 10 VDC control span
Weight
3 lbs [1.4 kg] with case
Wiring Diagram
Application
The ZG-X40 is a 40 VA, 120 to 24 VAC transformer. It is
designed so that both the primary and secondary leads exit
through the same side of a 4 1/4" square outlet box cover.
With this design, all wiring can be done inside a standard
J-box with a minimum amount of labor.
Wire Specification
No. 18 AWG leads, 6 1/2" length
Termination
Color
Primary White-Black
Secondary
Yellow-Yellow
Maximum Number of Like Actuators per Transformer
Transformer ZG-X40
40 VA, 120 to 24 VAC Transformer
ZG-X40
120 VAC
24 VAC
Yellow
Yellow
White
Black
4 1/4
4 1/4
2 3/4
Technical Data
ZG-X40
Primary Voltage
120 VAC 50/60 Hz
Secondary Voltage
24 VAC
Max VA Rating
40 VA
Connections
6 1/2" leads with stripped ends
Type
Class 2
Mounting Method
4 1/4" square outlet box cover
Agency Approvals
UL 1585, CSA 22.2 #66
Model #
Qty
TNMB24-3
11
TNMB24-SR
13
TAMB24-3
8
TAMB24-SR
8
TGMB24-3 6
TGMB24-SR
5
Model #
Qty
TAF24. .
4
TNF24 (-S)
5
TNF 120 (-S)
5
TNF24-SR 6
TLF24 8
TLF24-SR 8
Dimensions
Refers to appropriate actuator documentation for specific VA ratings.
Dimensions
[All numbers in brackets are in millimeters.]
I20683 - Subject to change.
Summary of Contents for TRANE TAF Series
Page 7: ...Notes Work Pad 7 I20683 Subject to change...
Page 27: ...27 I20683 Subject to change TAF Notes Work Pad...
Page 57: ...57 I20683 Subject to change TLF Notes Work Pad...
Page 73: ...73 I20683 Subject to change TTF Notes Work Pad...
Page 98: ...98 I20683 Subject to change Notes Work Pad...
Page 165: ...165 I20683 Subject to change Wiring Guide Notes Work Pad...