–6–
M-3425 Generator Protection Relay
STANDARD PROTECTIVE FUNCTIONS (
cont.)
Device
Setpoint
Number
Function
Ranges
Increment
Accuracy
†
RMS Overvoltage
Pickup #1, #2
5 to 180 V
1 V
!
0.5 V or
!
0.5%
!
0.8 V to
!
0.75%*
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
!
1 Cycle or
!
1%**
*When both RMS and Line-Ground to Line-Line is selected.
**When RMS (total waveform) is selected, timing accuracy is +20 cycles or
!
1%.
RMS Overvoltage, Neutral
Pickup #1, #2
5.0 to 180.0 V
0.1 V
!
0.5 V to
!
0.5%
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
!
1 Cycle or
!
1%
VT Fuse-Loss Detection
A VT fuse-loss condition is detected by using the positive and negative sequence components
of the voltages and currents. VT fuse-loss output can be initiated from internally generated logic
or from input contacts.
Time Delay
1 to 8160 Cycles
1 Cycle
!
1 Cycle or
!
1%
Out of Step (mho characteristic)
Circle Diameter
0.1 to 100.0
Ω
0.1
Ω
!
0.1
Ω
or 5%
(0.5 to 500.0
Ω
)
(
!
0.5
Ω
or 5%)
Offset
–100.0 to 100.0
Ω
0.1
Ω
!
0.1
Ω
or 5%
(–500.0 to 500.0
Ω
)
(
!
0.5
Ω
or 5%)
Impedance Angle
0° to 90°
1°
!
1°
Blinder
0.1 to 50.0
Ω
0.1
Ω
!
0.1
Ω
or 5%
(0.5 to 250.0
Ω
)
(
!
0.5
Ω
or 5%)
Time Delay
1 to 8160 Cycles
1 Cycle
!
1 Cycle or
!
1%
Trip on mho Exit
Enable/Disable
Pole Slip Counter
1 to 20
1
Pole Slip Reset
1 to 8160 Cycles
1 Cycle
!
1 Cycle or
!
1%
Frequency
Pickup #1,#2,#3,#4
50.00 to 67.00 Hz
0.01 Hz
!
0.02 Hz
40.00 to 57.00 Hz*
Time Delay #1–#4
2 to 65,500 Cycles
1 Cycle
!
2 Cycles or
!
1%
The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range of 47 to
53 Hz. Beyond these ranges, the accuracy is
!
0.1 Hz.
* This range applies to 50 Hz nominal frequency models.
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 A CT secondary rating.
59
59N
60
FL
81
78
Summary of Contents for M-3425
Page 1: ...Instruction Book M 3425 Generator Protection ...
Page 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Page 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Page 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Page 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Page 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Page 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Page 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...