M-3425 Instruction Book
6–18
21 Phase Distance (#1 or #2) Line to Ground
VOLTAGE INPUTS:Configuration V1
CURRENT INPUTS:Configuration C1
TEST SETTINGS:
Diameter
P
ohms
(0.1 to 100)
1 Amp CT Rating
(0.5 to 500.0)
Offset
O
ohms
(–100 to 100)
1 Amp CT Rating
(–500.0 to 500.0)
Impedance Angle
A
Degrees
(0 to 90)
Time Delay
D
cycles
(1 to 8160)
Programmed Outputs
Z
output
(1 to 8)
VT Configuration
Line-Ground
Functions 27, 27TN, 32, 40
Disable
Functions 50/27, 51V
Disable
Functions 60FL, 21 (1 or 2)
Disable
Functions 78, 87
Disable
Delta-Y Transform
Disable
■
■
■
■
■
NOTE: It would be efficient to disable the function with the higher “reach” (Diameter plus Offset)
setting first (lower current), and test the lower reach setting operation, since the higher reach
setting operation can be tested without disabling the lower setting.
1.
Disable functions as shown. Refer to Section 3.2, Initial Setup Procedure/Settings, Configure
Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect input in Configuration V1 and C1 as designated above. Refer to Section 6.1, Equipment/Test
Setup for configurations.
4.
The level of current at which operation is to be expected for an individual setting is as follows:
a. Define “reach” as R ohms = (P ohms + O ohms),[O, usually set at zero ohms].
b. Define “current” as I = ((Selected Voltage)IR ohms). The voltage level may be selected based
on the desired test current level
5.
Pickup Test: Set the three-phase voltages to the Selected Voltage value from step 4b. Set the
phase angle between the voltage and current inputs at (A) degrees from setting above. Hold the
TARGET RESET button in and slowly increase the three-phase currents on the input until the
appropriate 21 PHASE DISTANCE LED light goes on, or the pickup indicator operates on the
computer target screen. The level should be equal to I calculated in step 4 with the resulting
impedance
"
0.1 ohms or 5%. Release the TARGET RESET button and decrease the INPUT
CURRENTS, and OUTPUT LEDs will go out. Press TARGET RESET button to remove targets.
6.
Time Test: With output contacts (Z) connected to stop the timer, apply approximately 110% of
the current (I) found in step 4, and start timing. The contacts will close after D cycles within
"
1
cycle or
"
1%.
7.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
Summary of Contents for M-3425
Page 1: ...Instruction Book M 3425 Generator Protection ...
Page 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Page 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Page 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Page 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Page 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Page 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Page 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...