6–39
Testing – 6
60FL VT Fuse Loss Detection
VOLTAGE INPUTS: Configuration V1
CURRENT INPUTS: Configuration C1
TEST SETTINGS:
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
OUT
(1 to 8)
Function 27, 27TN, 32, 87
Disable
■
■
■
■
■
NOTE: It is necessary for “FL” to be designated as an initiating input (see Section 2.3, Setpoints and
Time Settings) before this function can be tested.
1.
Disable functions as shown. See Section 3.2, Initial Setup Procedure/Settings, Configure Relay
Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 and C1 designated above. See Section 6.1, Equipment/Test
Setup for configurations.
4.
Adjust the three-phase voltage source to Nominal volts, and the three-phase current source to
Nominal amps.
5.
Time Test: With output contacts connected to the timer, remove the A phase voltage input and
start timing, and the 60FL V.T. FUSE LOSS LED and output Z LEDs will light or the pickup
indicator operates on the computer target screen. The operating time will be D cycles within
"
1
cycle or
"
1%.
6.
Reconnect the phase A voltage and press TARGET RESET button to remove targets.
7.
Repeat steps 5 and 6 for phases B and C.
8.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
Summary of Contents for M-3425
Page 1: ...Instruction Book M 3425 Generator Protection ...
Page 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Page 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Page 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Page 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Page 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Page 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Page 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...