Fig. 42
THINK Controller
Fig. 43
5 LED Receiver (
Inputs
Reset button: Used for user reset.
Outputs
1st Green LED
Mains On
2nd Green LED
Communication status
1st Yellow LED
Engine burner status
2nd Yellow LED
Supplementary burner status
Red LED
Fault status
10.13 To Configure the THINK Controller as a Room Sensor
IMPORTANT: Before running the appliance ensure parameter 5700 has been set according to the type of system installed.
See
for system types and
k for the change procedure.
1. To configure the THINK Controller to act as a room sensor parameter 40 must be changed from Operator Unit 1 (the appliance) to Room Unit 1 (room unit).
2. To access parameter 40
Press the Menu Button to reveal 'Information'.
Press and hold Easy Menu and Menu Buttons until 'Enduser' is revealed.
Turn the Selector Button to highlight 'commissioning' and press to select.
Turn the Selector Button to highlight 'operator section' and press to select.
Turn the Selector Button to highlight 'Used as' and press to select,
whilst flashing turn the Selector Button to show the desired room unit and press to select.
page 47
3. Press the menu button repeatedly until the standard screen is available. The Programmable Room Unit symbol should be shown on the screen if the THINK Controller has
been configured correctly, see
.
4. If a second THINK Controller is to be used to control either a second heating circuit or to remain on the appliance then the parameter settings are slightly altered, see
.
5. To complete the reconfiguring the main PCB must be rebooted with the information from the THINK Controller, so switch off the appliance and then repower after 10
seconds. The THINK Controller will now act as a programmable room sensor when mounted into a wall cradle.
6. The THINK Controller's can be replaced on the appliance at any time but to avoid conflict and Error 84 address collision problems, parameter 40 must be reconfigured back
to 'Operator Unit 1'.
Summary of Contents for ECOGEN 24/1.0
Page 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Page 70: ...page 70 16 2 Milligrid 24 way Connector...
Page 71: ...page 71 16 3 14 way Connector...
Page 72: ...page 72 16 4 Engine Circuit...
Page 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Page 74: ...page 74 16 6 External Connections External Wiring...
Page 85: ...page 87...
Page 86: ...page 88...
Page 87: ...page 89 Section P...
Page 88: ...page 90...
Page 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Page 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Page 92: ...page 97...