17.3 Error Codes
Below are shown the error codes which will be displayed on the THINK Controller if a fault occurs on the appliance. Error Codes shown on remote interfaces may be collective
codes refer to the THINK Controller for the exact error message. More than one error may be present so that subsequent error codes will be shown as the original error is reset.
The occurrence of an error code will prevent some or all of the operations of the appliance.
Error codes specific to the running of the engine will not prevent the supplementary burner from operating and visa verse.
There are three levels of error code with associated reset procedures as follows:
1. Automatic reset (AR) Examples are mainly to do with temperature sensing but also include monitoring of the mains supply. Automatic reset only occurs if the fault
condition is eliminated.
2. User reset (UR) An example would be the restoration of the gas supply to enable ignition.
3. Service reset (SR) arises when a reset of the condition needs to be accompanied by the attendance of a service engineer.
There are two special conditions:
1. Automatic reset after power down (ARP) an automatic reset can only occur after the electrical supply is interrupted. Usually this implies data corruption and is in effect
a 'reboot' of the PCB.
2. No restart possible (NRP) occurs if there is corruption of stored data for instance and implies that the PCB will have to be replaced.
page 77
17.4 List of Error Codes
In the table below: PCB = Main Control Board, BCU = Burner Control Unit.
Error code:
Display
Description
Lockout/Reset
action
Fault
Section
Eng
Sup
10: Outside
sensor
Fault outside temp sensor
AR
AR
B
20: Boiler
sensor 1
Fault boiler flow temp sensor
AR
AR
C
40: Return
sensor 1
Fault return temp sensor boiler
AR
AR
C
50: DHW tank
sensor
Fault DHW1 sensor
AR
AR
B
60: Room
sensor 1
Fault room temp sensor HC1
AR
AR
B
65: Room
sensor 2
Fault room temp sensor HC2
AR
AR
B
83: BSB short
circuit
Boiler system bus shortcircuit
AR
AR
B
84: BSB
address
collision
More then 1 room units are assigned to the same HC Assign one of them to HC2 or
assign QAA7x not as room unit
ARP
ARP
B
85: Radio
communication
Communication to radio device interrupted
AR
AR
B
91: Data loss
in EEPROM
Failure in Class BSW: Irreparable data loss in EEPROM
NRP
NRP
B
92: Device
electronics
error
RAM failure, HBC processor register failure, blocking chain undefined (toggling), safety
chain discrepancy. Reset: Press Service Reset within 20 seconds after Power up
NRP
NRP
B
95: Time of
day invalid
The real time clock unit detected corrupted time of day.
B
96: Minor SW
failure
Failure in Class BSW: Stack overflow or program sequence failure
AR
AR
B
97: SW or HW
failure
Failure in EGCSW which causes nonvolatile lock.
NRP
NRP
B
102: Clock
without backup
The charging of the clock backup ran out
AR
AR
B
114: Shut'd
flue gas
Shutdown due to flue gas thermostat of safety chain
SR
SR
D
Summary of Contents for ECOGEN 24/1.0
Page 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Page 70: ...page 70 16 2 Milligrid 24 way Connector...
Page 71: ...page 71 16 3 14 way Connector...
Page 72: ...page 72 16 4 Engine Circuit...
Page 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Page 74: ...page 74 16 6 External Connections External Wiring...
Page 85: ...page 87...
Page 86: ...page 88...
Page 87: ...page 89 Section P...
Page 88: ...page 90...
Page 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Page 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Page 92: ...page 97...