![Baxi ECOGEN 24/1.0 Installation & Servicing Instructions Manual Download Page 49](http://html1.mh-extra.com/html/baxi/ecogen-24-1-0/ecogen-24-1-0_installation-and-servicing-instructions-manual_2711788049.webp)
7. When a THINK Controller is mounted in a wall cradle, the 5 LED Receiver fills the space on the appliance. It acts as an indicator see
carried out as they cannot be performed remotely.
Wiring connections to appliance see
Wired THINK Controller Wall Cradle Control Terminal Function
1. Power supply 12v
2. Ground (0v)
3. Data Signal (+v)
Fig. 44
10.14 To Install the 5 LED Receiver and THINK Controller
1. Isolate the appliance.
2. Remove the 5LED Receiver from the wall cradle (as supplied).
3. Connect the wire terminals between the room unit wall cradle and the appliance controls installation area, using wire suitable for 12v. (<200m)
4. Install the wall cradle in a suitable room or hall way. (see
5. Make sure the wall cradle is not in a position where it can be accidentally knocked or tampered with.
6. Remove the THINK Controller from the appliance and place it in the wall cradle.
7. Place the 5LED Receiver onto the appliance.
8. Switch on the appliance.
9. If the THINK Controller has not been configured as a Room Sensor correctly, you may see error 84: BSB collision. If this does happen, repeat from
paragraph 2 while the THINK Controller is on the wall cradle. Once the parameters have been checked down power the appliance for 10 seconds and then switch the
appliance back on.
page 48
10.15 Room Unit Installation Procedure
1. Room unit location: The wall cradle should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen such that the sensor can capture the room temperature as accurately as possible without getting adversely affected by
direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor) (
).
There must be sufficient clearance around the unit, enabling it to be fitted and removed.
Important : A TRV should not be fitted to the radiator in the same room as the room sensor.
If a TRV has been installed on this radiator, the TRV must remain set open at all times,
therwise the house holder will experience room temperature control problems.
Summary of Contents for ECOGEN 24/1.0
Page 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Page 70: ...page 70 16 2 Milligrid 24 way Connector...
Page 71: ...page 71 16 3 14 way Connector...
Page 72: ...page 72 16 4 Engine Circuit...
Page 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Page 74: ...page 74 16 6 External Connections External Wiring...
Page 85: ...page 87...
Page 86: ...page 88...
Page 87: ...page 89 Section P...
Page 88: ...page 90...
Page 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Page 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...