![Baxi ECOGEN 24/1.0 Installation & Servicing Instructions Manual Download Page 15](http://html1.mh-extra.com/html/baxi/ecogen-24-1-0/ecogen-24-1-0_installation-and-servicing-instructions-manual_2711788015.webp)
page 17
7.6 Heating Plant Emissions Rate (HPER)
1. To enable the house holder to claim the Feed in tariff (FIT) the heating plant emission rate must be calculated and entered into the MCS certification submission and
recorded in the Micro chp system commissioning checklist benchmark sheets at the back of these instructions.
See the Baxi website to calculate the HPER values
http://www.baxi.co.uk/products/getfitwithbaxiecogen.htm.
Calculate perform http://www.ecogen.baxi.co.uk/mcsperform
2. To find the Heating Plant Emissions Rates for Plant Size Ratios between 0.5 and 4.0 please see the table below.
PSR
HPER
0.5
0.295
0.6
0.282
0.7
0.269
0.8
0.256
0.9
0.243
1
0.231
1.1
0.225
1.2
0.219
1.3
0.213
1.4
0.207
1.5 to 4 0.201
7.7 Electrical Connection General
1. The product must be installed by a competent trained electrician that has been on a Baxi approved course.
2. The fuse rating of the securable isolator shall be 13A.
3. A mains supply of 230V ~50Hz is required.
4. Mains wiring external to the product must be in accordance with the current IEE (BS 7671) Requirements for Electrical Installation (Wiring Regulations) and any local
regulations.
5. Connection must be made in a way that allows complete isolation of the electricity supply a double pole switch serving only the product and system controls. The manual
isolation switch shall be capable of being secured in the off (isolation) position; this switch is to be located in an accessible position within the customer's installation.
6. Connection to the mains must be made in accordance with the latest addition of the Engineering Recommendation G83 Recommendations for the connection of Small
Scale Embedded Generators (SSEG) in parallel with public low voltage distribution networks.
7. The Distribution Network Operator (DNO) must be provided with information regarding the SSEG Guidance Notes, installation on the day of commissioning. A notification
sheet is provided which should be completed and sent to your Distribution Network Operator (DNO) alternatively this may be done through the DNO's website.
8. Two labels (
) are provided to be placed at:
a) The consumer unit
b) The appliance
9. The installer shall provide labeling at the supply terminals (fused cutout). meter position, consumer unit and at all points of isolation within the users premises to indicate
the presence of a microCHP unit. An example of the warning label to be left on site is shown (
).
10. There are two ways in which the Ecogen 24/1.0 appliance can be electrically installed.
Connection by dedicated circuit (
Connection into an existing final circuit (
Fig. 12
Fig. 12a
page 18
7.7 Installer information
11. Whichever of the two options is chosen, it is imperative that the safety of the electrical installation is not impaired by the installation of the Ecogen 24/1.0.
12. To enable the FIT to be claimed the electricity generated and exported must be monitored by meters installed into the electricity supply as shown in
for the export either bidirectional meters as in
, or by leaving the existing meter and adding an additional meter as in
. An extra meter must be
added just before the appliance to measure the electrical generation. The serial number must be submitted for MCS submission and recorded in both the DNO leaflet and
the Micro CHP system commissioning checklist benchmark sheets at the back of these instructions.
13. The Ecogen 24/1.0 must not be connected to an installation by means of a plug and socket.
14. The essential criteria which must be met are given below for both options.
15. Connection of an Ecogen to a dedicated circuit
Summary of Contents for ECOGEN 24/1.0
Page 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Page 70: ...page 70 16 2 Milligrid 24 way Connector...
Page 71: ...page 71 16 3 14 way Connector...
Page 72: ...page 72 16 4 Engine Circuit...
Page 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Page 74: ...page 74 16 6 External Connections External Wiring...
Page 85: ...page 87...
Page 86: ...page 88...
Page 87: ...page 89 Section P...
Page 88: ...page 90...
Page 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Page 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Page 92: ...page 97...