10.10 SPlan with 2nd Heating Circuit
1. The appliance MUST have a permanent Live/Neutral/Earth connection. The pump must be connected to the appliance as shown.
2. Set parameter 5700 to '3' for two heating circuits see
3. To control the second heating circuit a second THINK Controller is required this is available as an optional extra. For guidance on installing the second THINK Controller
see
Use either a cylinder sensor or thermostat as in