9440300990 Rev J
139
DECS-250
BESTlogic™
Plus
Name
Description
Symbol
Remote Inputs
IN15 - IN24
True when Remote Input x is active.
(Available when an optional CEM-2020 is
connected.)
Virtual Inputs
VIN1 - VIN6
True when Virtual Input x is active.
Status Inputs
Anticipatory Sync
Selected
True when Anticipatory is selected. (Synchronizer
screen)
Auto Mode Active
True when the unit is in Auto mode (AVR).
Bus Dead
True when the Bus Dead condition settings have
been exceeded. (Available when the controller is
equipped with the optional Auto synchronizer, style
number xxxxAxx)
Bus Failed
True when the Bus Stable condition settings are
not met. (Available when the controller is equipped
with the optional Auto synchronizer, style number
xxxxAxx)
Bus Stable
True when the Bus Stable condition settings have
been exceeded. (Available when the controller is
equipped with the optional Auto synchronizer, style
number xxxxAxx)
Auto Sync
Enabled
True when DECS auto-sync is enabled. (Available
when the controller is equipped with the optional
Auto synchronizer, style number xxxxAxx)
Dead Bus Close
Request
True when this option is user-enabled; a dead bus
is closed automatically upon detection. False when
this option is disabled; a dead bus will remain
open. (Available when the controller is equipped
with the optional Auto synchronizer, style number
xxxxAxx)
External Tracking
Active
True when external tracking is running.
Failed To Buildup
True when the Failed to Buildup alarm is active.
FCR Active
True when the unit is in FCR mode.
Field Flash Active True when field flash is active.
Field Short
Circuit Status
True when a field short circuit condition is detected.
FVR Active
True when the unit is in FVR mode.
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......