9440300990 Rev J
311
DECS-250
Analog Expansion Module
Figure 176. Remote Analog Input Settings
A
Label Text:
An alphanumeric character string with a maximum of 64 characters.
B
Input Type:
Voltage or Current.
C
Hysteresis:
Adjustable from 0 to 100% in 0.1% increments.
D
Arming Delay:
Adjustable from 0 to 300 s in 1 s increments.
E
Stop Mode Inhibit:
Yes or No.
F
Param Min:
Adjustable from
–
9999.0 to +9999.0 in increments of 0.1
G
Min Input Current:
Adjustable from 4 to 20 mA in 0.1 mA increments.
H
Min Input Voltage:
Adjustable from 0 to 10 V in 0.1 V increments.
I
Param Max:
Adjustable from
–
9999.0 to +9999.0 in increments of 0.1.
J
Max Input Current:
Adjustable from 4 to 20 mA in 0.1 mA increments.
K
Max Input Voltage:
Adjustable from 0 to 10 V in 0.1 V increments.
L
Mode:
Disabled, Over, or Under.
M
Threshold:
Adjustable from
–
9999.0 to +9999.0 in increments of 0.1.
N
Activation Delay:
Adjustable from 0 to 300 s in 1 s increments.
RTD Inputs
BESTCOMSPlus
®
Navigation Path:
Settings, Programmable Inputs, Remote RTD Inputs
HMI Navigation Path:
Settings, Programmable Inputs, Remote RTD Inputs
The AEM-2020 provides eight user-configurable RTD inputs that can annunciate a latching or non-
latching alarm. The RTD inputs are always monitored and their status is displayed on the appropriate
metering screens. To make identifying the RTD inputs easier, a user-assigned name
A
can be given to
each input.
Select the amount of hysteresis
B
needed to prevent rapid switching of the alarm. Select the RTD type
C
. A
user-adjustable arming delay
D
allows configuration of the RTD input threshold monitoring in one of two
ways. (1) When the arming delay is set to zero, threshold monitoring is performed all the time, whether or
not excitation is enabled. (2) When the arming delay is set to a non-zero value, threshold monitoring
begins when the arming delay time has expired after system startup is complete. An out-of-range alarm,
configured on the
Alarm Configuration, Alarms
screen in BESTCOMS
Plus
, alerts the user of an open or
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......