90
9440300990 Rev J
Event Recorder
DECS-250
Figure 84. Trend Log Setup
A
Trending Enable:
Select Enabled or Disabled.
B
Trending Log Parameters:
Select NO Level Trigger, Vab: PhA-PhB L-L Voltage {p.u}, Vbc: PhB-PhC L-L
Voltage {p.u}, Vca: PhC-PhA L-L Voltage {p.u}, Vbus: Bus Voltage {p.u}, Ia : Phase A Current {p.u}, Ib:
Phase B Current {p.u}, Ic: Phase C Current {p.u}, Vavg: Avg L-L Voltage {p.u}, Iavg: Avg Line Current
{p.u}, Iaux: Cross Current Input {p.u}, Vfd: Field Voltage {p.u}, Ifd: Field Current {p.u}, Vaux: Aux Voltage
Input {p.u}, kW: Real Power {p.u.}, kvar: Reactive Power {p.u.}, kVA: Total Power {p.u.}, PF: Power
Factor, V1: Positive Sequence Voltage {p.u.}, V2: Negative Sequence Voltage {p.u.}, I1: Positive
Sequence Current {p.u.}, I2: Negative Sequence Current {p.u.}, G Hz: Generator Frequency (Hz), B Hz:
Bus Frequency {Hz}, Test: Frequency Response Signal {p.u.}, or Ptest: Time Response Signal {p.u.},
TermF: Terminal Frequency Deviation {%}, CompF: Compensated Frequency Deviation, PssKW: Pss
Electric Power {p.u.}, Vtmag: PSS Term Voltage,x2 : Speed HP #1,WashW : Washed Out Speed {p.u.},x5
: Power HP #1 {p.u.}, WashP: Washed Out Power {p.u.}, x7: Mechanical Power {p.u.}, x8: Mechanical
Power LP #1, x9: Mechanical Power LP #2, x10: Mechanical Power LP #3, x11: Mechanical Power LP #4,
MechP: Filtered Mechanical Power {p.u.}, Synth: Synthesized Speed {p.u.}, Tflt1: Torsional Filter #1
{p.u.}, x29: Torsional Filter #2 {p.u.}, x15: Lead-Lag #1 {p.u.}, x16: Lead-Lag #2 {p.u.}, x17: Lead-Lag #3
{p.u.}, x31: Lead-Lag #4 {p.u.}, Prelim: Pre-Limit Output {p.u.}, Post: Post-Limit Output {p.u.}, POut: Final
PSS Output {p.u.}, CntOp: Control Output {p.u.}, TrnOp: Internal State {p.u.}, ErrIn: Avr Error Signal,
OelOutput: OEL Controller Output, UelOutput: UEL Controller Output, SclOutput: SCL Controller Output,
varLimOutput: var Limiter Output, NullBalance: Null Balance Level {p.u.}, PositionInd: Position Indication
{p.u.}, AvrOut, FcrErr, FcrState, FcrOut, FvrErr, FvrState, FvrOut, var/PfErr, var/PfState, var/PfOut,
OelState, UelState, SclState, varLimState, Droop,Rcc, OelRef, UelRef, SclIRef, SclPfRef, varLimRef,
ProgrammableDiagnotic1, ProgrammableDiagnotic2, ProgrammableDiagnotic3,
ProgrammableDiagnotic4, ProgrammableDiagnotic5, or ProgrammableDiagnotic6.
C
Trending Duration:
Adjustable from 1 to 720 hours in 1 hour increments.
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......