9440300990 Rev J
103
DECS-250
Stability Tuning
Figure 99. PID Calculator
A
K
p
– Proportional Gain
: Read-only, calculated gain value.
B
K
i
– Integral Gain
: Read-only, calculated gain value.
C
K
d
– Derivative Gain
: Read-only, calculated gain value.
D
T’do – Gen. Time Constant:
Select a value within the range of 1 to 15 seconds.
E
T
e
– Exciter Time Constant
: Select a value within the range of 0.04 to 1.0 seconds.
F
Use Default Exciter Time Constant
: Select or deselect.
G
T
d
– Derivative Time Constant
: Adjustable from 0 to 1 in 0.01 increments.
H
K
a
– Voltage Regulator Gain
: Adjustable from 0 to 1 in 0.001 increments.
I
Apply Gain Parameters Button
: Click button to apply gain parameters.
J
Close Button
: Click button to close PID calculator.
K
Generator Information:
Enter up to 30 alphanumeric characters.
L
Add Record:
Adds a PID record.
M
Remove Record:
Removes a PID record.
Auto Tuning
During commissioning, excitation system parameters may not be known. These unknown variables
traditionally cause the commissioning process to consume large amounts of time and fuel. With the
development of auto tuning, the excitation system parameters are now automatically identified and the
PID gains are calculated using well-developed algorithms. Automatically tuning the PID controller greatly
reduces commissioning time and cost. The auto tuning function is accessed by clicking the
Auto Tune
button (Figure 98, Locator H). BESTCOMS
Plus
must be in Live Mode in order to begin the auto tuning
process. The auto tuning window (Figure 100) provides options for choosing the PID Design Mode
A
and
the Power Input Mode
B
. When the desired settings are selected, the
Start Auto Tune
C
button is clicked to
start the process. After the process is complete, click the
Save PID Gains (Primary)
D
button to save the
data.
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......