9440300990 Rev J
49
DECS-250
Protection
Field protection provided by the DECS-250 includes field overvoltage, field overcurrent, an exciter diode
monitor, and power input failure.
Field Overvoltage
A field overvoltage condition occurs when the field voltage exceeds the field overvoltage threshold
A
for the
duration of the field overvoltage time delay
B
. Field overvoltage protection can be enabled and disabled
C
without altering the pickup and time delay settings. Field overvoltage pickup and trip elements in
BESTlogic
Plus
can be used in a logic scheme to initiate corrective action in response to the condition.
BESTlogic
Plus
field overvoltage settings are illustrated in Figure 36.
Figure 36. Field Overvoltage Protection Settings
A
Field Overvoltage Pickup (V)
: Adjustable from 0 to 325 Vdc in 1 Vdc increments.
B
Field Overvoltage Time Delay (s)
: Adjustable from 0.2 to 30 seconds in 0.1 second increments.
C
Field Overvoltage Mode
: Select Disabled or Enabled.
Field Overcurrent
A field overcurrent condition is annunciated when the field current exceeds the field overcurrent pickup
level
A
for the duration of the field overcurrent time delay. Depending on the selected timing mode
B
, the
time delay can be fixed or related to an inverse function. Definite timing mode uses a fixed time delay
C
. In
inverse timing mode, the time delay is shortened in relation to the level of field current above the pickup
level. The time dial
D
setting acts as a linear multiplier for the time to an annunciation. This enables the
DECS-250 to approximate the heating characteristic of the generator and generator step-up transformer
during overexcitation. The field current must fall below the dropout ratio (95%) for the function to begin
timing to reset. The following equations are used to calculate the field overcurrent pickup and reset time
delays.
𝑡𝑡
𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝
=
𝐴𝐴
×
𝑇𝑇𝑇𝑇
𝐵𝐵
+
√𝐶𝐶
+
𝑇𝑇
×
𝑀𝑀𝑀𝑀𝑀𝑀
Equation 9. Inverse Field Overcurrent Pickup
Where:
t
pickup
= time to pick up in seconds
A
= -95.908
B
= -17.165
C
= 490.864
D
= -191.816
TD
= time dial setting <0.1, 20>
MOP = multiple of pickup <1.03, 205>
𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇
𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟
=
0.36 ×
𝑇𝑇𝑇𝑇
(
𝑀𝑀𝑀𝑀𝑀𝑀
𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟
)
2
−
1
Equation 10. Inverse Field Overcurrent Reset
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......