PROFIBUS Communication
DECS-250
PROFIBUS Parameters
PROFIBUS parameters are listed in Table 39. Instances with names ending in “cyclic” are automatically
transmitted at a periodic rate. All other instances are acyclic and transmitted only when requested by the
PLC.
Table 39. PROFIBUS Parameters
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Gen Metering Cyclic
1
Float
R
VAB GG
V
0 - 2000000000
Gen Metering Cyclic
1
Float
R
VBC GG
V
0 - 2000000000
Gen Metering Cyclic
1
Float
R
VCA GG
V
0 - 2000000000
Gen Metering Cyclic
1
Float
R
IA GG
Amp
0 - 2000000000
Gen Metering Cyclic
1
Float
R
IB GG
Amp
0 - 2000000000
Gen Metering Cyclic
1
Float
R
IC GG
Amp
0 - 2000000000
Gen Metering Cyclic
1
Float
R
Freq GG
Hz
10 - 180
Gen Metering Cyclic
1
Float
R
Total Watts AVG GG
Watt
-3.00E+14 - 3.00E+14
Gen Metering Cyclic
1
Float
R
Total VARS AVG GG
Var
-3.00E+14 - 3.00E+14
Gen Metering Cyclic
1
Float
R
Total S GG
VA
-3.00E+14 - 3.00E+14
Gen Metering Cyclic
1
Float
R
Total PF GG
PF
-1 - 1
Bus Metering Cyclic
2
Float
R
VAB GG
V
0 - 2000000000
Bus Metering Cyclic
2
Float
R
VBC GG
V
0 - 2000000000
Bus Metering Cyclic
2
Float
R
VCA GG
V
0 - 2000000000
Bus Metering Cyclic
2
Float
R
Freq GG
Hz
10 - 180
Field Metering Cyclic
3
Float
R
VX GG
V
-1000 - 1000
Field Metering Cyclic
3
Float
R
IX GG
Amp
0 - 2000000000
Setpoint Metering Cyclic
4
Float
R
Gen Voltage Setpoint GG
V
84 - 144
Setpoint Metering Cyclic
4
Float
R
Excitation Current Setpoint
GG
Amp
0 - 12
Setpoint Metering Cyclic
4
Float
R
Excitation Voltage Setpoint
GG
V
0 - 75
Setpoint Metering Cyclic
4
Float
R
Gen Var Setpoint GG
kvar
0 – 41.57
Setpoint Metering Cyclic
4
Float
R
Gen Pf Setpoint GG
PF
0.5 – -0.5
Synchronizer Metering
Cyclic
5
Float
R
Slip Angle GG
Deg
-359.9 - 359.9
Synchronizer Metering
Cyclic
5
Float
R
Slip Freq GG
Hz
n/a
Synchronizer Metering
Cyclic
5
Float
R
Voltage Diff GG
V
n/a
Limiter Status Cyclic
6
UINT8
R
Alarms OEL ALM
No Unit
Not Active=0, Active=1
Limiter Status Cyclic
6
UINT8
R
Alarms UEL ALM
No Unit
Not Active=0, Active=1
Limiter Status Cyclic
6
UINT8
R
Alarms SCL ALM
No Unit
Not Active=0, Active=1
Limiter Status Cyclic
6
UINT8
R
Alarms VAR
Limiter Active
No Unit
Not Active=0, Active=1
Limiter Status Cyclic
6
UINT8
R
Alarms
Underfrequency V/Hz
ALM
No Unit
Not Active=0, Active=1
HMI Indicators Cyclic
7
UINT8
R
DECSCONTROL
DECS NULL BALANCE
No Unit
Not Active=0, Active=1
HMI Indicators Cyclic
7
UINT8
R
DECSPSSMETER
DECS PSS ACTIVE
No Unit
Not Active=0, Active=1
HMI Indicators Cyclic
7
UINT8
R
DECSREGULATORMETER
DECS
INTERNAL TRACKING
ACTIVE
No Unit
Not Active=0, Active=1
HMI Indicators Cyclic
7
UINT8
R
DECSCONTROL DECS
PREPOSITION
No Unit
Active setpoint is not at a pre-
position value=0, Active setpoint is
at a pre-position value=1
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......