9440300990 Rev J
55
DECS-250
Protection
•
Kilowatthours
•
Negative Sequence Current
•
Negative Sequence Voltage
•
Positive Sequence Current
•
Positive Sequence Voltage
•
PSS Output
•
RTD Input 1, 2, 3, 4, 5, 6, 7, 8
•
Setpoint Position
•
Thermocouple 1, 2
•
Total kVA
•
Total kvar
•
Total kW
•
Tracking Error
If an optional Analog Expansion Module (AEM-2020) is used, any one of the following analog, RTD, and
thermocouple inputs may be selected.
•
Analog Input 1, 2, 3, 4, 5, 6, 7, or 8
•
RTD Input 1, 2, 3, 4, 5, 6, 7, or 8
•
Thermocouple 1 or 2
Protection can be always enabled or enabled only when the DECS-250 is enabled and supplying
excitation
C
. When protection is enabled only in Start mode, an arming time delay
D
can be used to delay
protection following the start of excitation.
A hysteresis function holds the protection function active for a user-defined percentage
E
above/below the
pickup threshold. This prevents repeated pickups and dropouts where the monitored parameter is
hovering around the pickup threshold. For example, with a hysteresis setting of 5% on a protection
element configured to pick up at 100 Aac of A-phase generator overcurrent, the protection element would
pick up when the current rises above 100 Aac and remain picked up until the current decreases below 95
Aac.
Each of the eight configurable protection elements has four individually-adjustable thresholds. Each
threshold can be set for pickup when the monitored parameter increases above the pickup setting (Over),
pickup when the monitored parameter decreases below the pickup setting (Under), or no pickup
(Disabled)
F
. The pickup level for the monitored parameter is defined by a threshold setting
G
. While the
threshold setting range is broad, you must use a value within the setting range limits for the monitored
parameter. Using an out-of-limits threshold will prevent the protection element from functioning. An
activation delay
H
serves to delay a protective trip after the threshold (pickup) level is exceeded.
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......