Synchronizer
DECS-250
bus, the DECS-250 uses the breaker closing time
D
to calculate the optimum time to close the breaker. For
a pulse-controlled generator breaker, the breaker open
E
and close
F
pulse times are used by the DECS-
250 when issuing open and close commands to the breaker. When setting the pulse times, the open and
close times should be set at or longer than the breaker closing time setting.
If desired, breaker closure is possible during a dead bus condition
G
and/or dead generator condition
H
.
Caution
Use caution when connecting a “dead” generator to a “dead” bus.
Undesired system damage can occur if the bus becomes energized
while a “dead” generator is connected to it.
Figure 12. Breaker Hardware Configuration Settings
A
Breaker Close Wait Time
: Adjustable from 0.1 to 600 s in 0.1 s increments.
B
Gen Breaker
: Select Configured or NOT Configured.
C
Contact Type
: Select Pulse or Continuous.
D
Breaker Closing Time
: Adjustable from 0 to 800 ms in 5 ms increments.
E
Open Pulse Time
: Adjustable from 0.01 to 5 s in 0.01 s increments. Setting is available only when
Contact Type is Pulse.
F
Close Pulse Time
: Adjustable from 0.01 to 5 s in 0.01 s increments. Setting is available only when
Contact Type is Pulse.
G
Dead Bus Close
: Select Disabled or Enabled.
H
Dead Gen Close Enable
: Select Disabled or Enabled.
Generator and Bus Condition Detection
BESTCOMSPlus Navigation Path:
Settings Explorer, Synchronizer/Voltage Matching, Bus Condition
Detection
HMI Navigation Path:
Settings, Sync/Voltage Matching, Bus Condition Detection
The DECS-250 monitors the voltage and frequency of the generator and bus for determining when a
breaker closure is appropriate. Generator and bus condition detection settings are illustrated in Figure 13.
Generator Condition
A dead generator is recognized by the DECS-250 when the generator voltage decreases below the dead
generator threshold
A
for the duration of the dead generator activation delay
B
.
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......