DECS-250
Analog Expansion Module
Each thermocouple input can be independently configured for over or under mode
E
to annunciate an
alarm when the thermocouple input signal falls beyond the threshold
F
. Alarms are configured on the
Alarm
Configuration, Alarms
screen in BESTCOMS
Plus
. A user-adjustable activation delay
G
setting delays
alarm annunciation after the threshold has been exceeded.
The remote thermocouple inputs are incorporated into a BESTlogic
Plus
programmable logic scheme by
selecting them from the
I/O
group in BESTlogic
Plus
. For more details, refer to the
BESTlogicPlus
chapter.
BESTCOMS
Plus
®
settings for remote thermocouple inputs are illustrated in Figure 178. Remote
Thermocouple Input #1 is shown.
Figure 178. Remote Thermocouple Input Settings
A
Label Text:
An alphanumeric character string with a maximum of 64 characters.
B
Hysteresis:
Adjustable from 0 to 100% in 0.1% increments.
C
Arming Delay:
Adjustable from 0 to 300 s in 1 s increments.
D
Stop Mode Inhibit:
Yes or No.
E
Mode:
Disabled, Over, or Under.
F
Threshold:
Adjustable from 32 to 2,507
°
F in 1
°
F increments.
G
Activation Delay:
Adjustable from 0 to 300 s in 1 s increments.
Analog Outputs
BESTCOMSPlus Navigation Path:
Settings, Programmable Outputs, Remote Analog Outputs
HMI Navigation Path:
Settings, Programmable Outputs, Remote Analog Outputs
The AEM-2020 provides four analog outputs.
Make a parameter selection
A
and select the output type
B
. An out-of-range alarm configured on the
Alarm
Configuration, Alarms
screen in BESTCOMS
Plus
, alerts the user of an open or damaged analog output
wire. An out-of-range activation delay
C
setting delays alarm annunciation.
Ranges must be set for the selected output type. Param Min
D
correlates to Min Output Current
E
or Min
Output Voltage
F
and Param Max
G
correlates to Max Output Current
H
or Max Output Voltage
I
.
The remote analog outputs are incorporated into a BESTlogic
Plus
programmable logic scheme by
selecting them from the
I/O
group in BESTlogic
Plus
. For more details, refer to the
BESTlogicPlus
chapter.
BESTCOMS
Plus
settings for remote analog outputs are illustrated in Figure 179. Remote Analog Output
#1 is shown.
Summary of Contents for DECS-250
Page 2: ......
Page 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Page 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Page 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Page 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Page 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Page 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Page 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Page 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Page 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Page 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Page 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Page 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Page 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Page 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Page 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Page 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Page 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Page 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Page 351: ......