The following baud rates can be selected:
Value
Baudrate
0
1 Mbit/s
1
800 kBit/s
2
500 kBit/s
3
250 kBit/s
4
125 kBit/s
5
100 kBit/s
6
50 kBit/s
7
20 kBit/s
8
10 kBit/s
9
Auto
Table 8.9: Baudrate-Coding
Check the LSS slaves answer to the command above:
7E4h
13h
00h
00h
00h
00h
00h
00h
00h
CAN-ID
Command
Error Code
Specific Error
Byte2
Byte3
Byte4
Byte5
Byte6
Table 8.10: Answer of LSS-slave
Error Code:
•
00h = OK
•
01h = Baudrate not supported
Specific Error:
•
00h = OK
•
FFh = Application specific error
Possibly the communication with the encoder fails after the configuration because the configuration tool and the
encoder might operate on different baud rates, so you have to change the baudrate configuration of your tool.
•
Before changing the baudrate you have to check the baudrate of the application.
Assure yourself that your configuration tool supports that baudrate! Make a note of
the selected baudrate (i.g. in this manual or on the encoders label)
8.2.6
Node-ID setting
Use the following command to change the encoder’s node ID:
7E5h
11h
Node-ID
00h
00h
00h
00h
00h
00h
CAN-ID
Command
Node-ID
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Table 8.11: set Node-ID
Valid Node IDs are 01h to 7Fh.
•
Mind leaving the LSS configuration mode after configuration (see above 8.2.4)!
Summary of Contents for BDG F-NH Series
Page 1: ...deutsch Konfigurationsanleitung english Configuration guide BDG F_ _ _ _ _ _ _ _ NH NV...
Page 2: ...www balluff com...
Page 3: ...deutsch Konfigurationsanleitung BDG F_ _ _ _ _ _ _ _ NH NV...
Page 4: ...www balluff com...
Page 67: ...english Configuration guide BDG F_ _ _ _ _ _ _ _ NH NV...
Page 68: ...www balluff com...
Page 105: ...www balluff com 38...
Page 129: ......