Table 10-1 Troubleshooting Guide
Symptom
Possible Cause
Suggested Solution
Line fuse blows or
circuit breaker trips.
The line fuse or
circuit breaker
installed is the
incorrect rating.
See Table 1-7 for the
correct line fuse or
circuit breaker rating.
Drive or Motor
Failure.
Check and replace
defective part.
Motor does not run.
On/Off AC Line
Switch is in the
OFF position.
Set the On/Off AC
Line Switch to the ON
position.
The Main Speed
Potentiometer is
set to zero speed.
Set the Main Speed
Potentiometer for the
desired speed.
The Main Speed
Potentiometer,
signal input, or
motor connection
are open.
Verify Main Speed
Potentiometer, signal
input, or motor
connections.
The Forward-Stop-
Reverse Switch
(when installed) is
set to the “STOP”
position.
Set the Forward-Stop-
Reverse Switch to
the “FORWARD” or
“REVERSE” position.