23
4.2 GROUND CONNECTION
Connect the ground (earth) wires from the AC line and motor to
Terminal Block TB1 (Terminal “GND”). See Figure 4-1.
4.3 MOTOR CONNECTION
Connect the motor to Terminal Block TB1 Terminals “U”, “V”,
and “W”. See Figure 4-2. Motor cable length should not exceed
100 ft (30 m) - special reactors may be required - consult your
local Baldor District Office. Be sure Jumper J2 is set to the
corresponding motor horsepower rating, as described in Section
7.2.
Note:
If the motor rotates in the incorrect direction, it will be necessary to
disconnect the AC line and change the position of the jumper on
CON2 from “F” to “R” or reverse any two motor leads.
4.4 RUN/FAULT RELAY CONNECTION
The Run/Fault Relay Output Contacts are located at TB2 and
can be used to turn on or off equipment or to signal a warning if
a fault has occurred or the drive is put into the Stop Mode*. See
Figure 4-2. The Run/Fault Relay Contact status for various drive
operating conditions is shown in Table 4-2. Also see Section 6.5.
Relay Contacts Ratings:
1 Amp at 30 Volts DC, 0.5 Amps at 125
Volts AC, and 0.25 Amps at 250 Volts AC.
*
In order for the Run/Fault Relay to give “Stop Mode” indication,
the optional Forward-Stop-Reverse Switch (Catalog No.
ID5FRS-2) must be installed.
Figure 4-2 Run/Fault Relay Output Connections
Relay Common
Normally Closed
Normally Open
TB2
Recommended Tightening Torque
lb-in (3.5), kg-cm (3)
Summary of Contents for ID5601-EO
Page 18: ...18 Figure 2 3 Drive Layout ...