38
8.2.1 Drive Set for Automatic Start and Reset (Factory
Setting)
The drive will automatically restart after an Undervoltage or
Overvoltage Fault has cleared. For an I
2
t Fault, be sure the fault
has been cleared before restarting the drive. Check the motor
current with an AC RMS responding ammeter. Also, the CL setting
may be set too low. See Section 7.6. For an I
2
t or Short Circuit
Fault, the drive must be restarted by setting the On/Off AC Line
Switch to the “OFF” position for a minimum of 5 seconds.
8.2.2 Drive Set for Manual Start and Reset
*
In Manual Start Mode, the drive must be manually restarted after
a fault has cleared, using the optional Forward-Stop-Reverse
Switch. If a Short Circuit or I
2
t Fault occurs, the drive must be
restarted by setting either the On/Off AC Line Switch to the “OFF”
position for a minimum of 5 seconds or setting the Forward-Stop-
Reverse Switch to the “STOP” position.
*
Note:
The optional Forward-Stop-Reverse Switch must be installed in
order to use the drive for Manual Start operation.