31
For 120Hz output with 60Hz motor, set Jumper J4 to the “2X”
position and be sure Jumper J5 is set to the “60Hz” position. For
100Hz output with 50Hz motor, set Jumper J4 to the “2X” position
and set Jumper J5 to the “50Hz” position. See Figure 6-6.
Figure 6-6 120Hz and 100Hz Drive Output Frequency
Selection
120 Hz Output with 60 Hz Motor
(J4 Installed in “2X” Position)
(J5 Installed in “60Hz” Position)
100 Hz Output with 50 Hz Motor
(J4 Installed in “2X” Position)
(J5 Installed in “50Hz” Position)
6.5 RUN/FAULT OUTPUT RELAY OPERATION (J6)
Jumper J6 is factory set to the “RUN” position for “Run” operation
of the Run/Fault Relay. For “Fault” operation of the Run/Fault
Relay, set Jumper J6 to the “FLT” position. See Figure 6-7.
Figure 6-7 Run or Fault Output Relay Operation Selection
“Run” Output Relay Operation
(Factory Setting)
(J6 Installed in “RUN” Position)
“Fault” Output Relay Operation
(J6 Installed in “FLT” Position)