- 34 -
Zones
Zones
ENT
Zone numbers
1 (1 .. . 32)
Zone type
Delay T1
Phisical input
CPN I.BA 1
Zone numbers:
For every “software” zone it is possible to associate a physical input corresponding to the “clamp” where
the detector was wired.
Press
(CLR)
to vary
To access other entries press
(
)
or
(
)
Press arrows
(
)
and
(
)
to position the cursor
Press
(ENT)
to confirm
Entries description
A -
CPN = CONTROL PANEL,
EXP= SATELLITE, KBD= KEYPAD
B -
n. x = SATELLITE ADDRESS (appears only if A = SAT/PAD)
C -
I.BA = BASIC INPUT
I.EX = EXTENSION INPUT
D -
n. x = INPUT NUMBER
Example:
In the example at the side, the software zone is linked to the physical input that
corresponds to -
SATELLITE n. 5
- connected on
BASIC INPUT- number 3
Zone type:
for every input line of the control panel it is possible to determine the type of line.
•
Not used:
the zone is not considered from the control panel analysis.
•
Istant:
zone that causes an immediate alarm when it unbalances with control panel armed.
•
Conditional:
immediate zone that is automatically excluded during the input and output time of a timed zone; in case of
more timed zones, reference must be made to that with the longest time. With control panel armed the unbalancing of this
input causes an immediate alarm when the output time or the return time are not in progress.
•
Dealy T1:
upon arming of the control panel the output time becomes active, signalled by the intermittent sound of the
keypad buzzer. After this time, if the input is unbalanced, the return time is made available, signalled by an intermittent, highly
frequent, sound; after expiry of this time an alarm is activated, unless the control panel has been in the mean time disarmed.
•
Inst. perm. esc. (Immediate permanent esclusion):
immediate zone that is automatically excluded if unbalanced at the
time of arming the control panel; it remains excluded until disarming of the same control panel.
•
T1 Perm. escl. (Timed Permanent esclusion):
these are timed zones with permanent exclusion. They are automatically
excluded if resulting unbalanced at the end of the output time; they remain excluded until disarming of the same control panel.
If it is balanced at the end of the output time, when it is next balanced, the zone will be timed with the input time.
•
Ist. temp. escl (Immediate with temporary esclusion):
it is automatically excluded if it results unbalanced upon arming
of the control panel; it is automatically included upon its re-balancing.
•
T1 Temp. escl. (Timed with temporary esclusion):
these are timed zones with permanent exclusion. They are automatically
excluded if resulting unbalanced at the end of the output time; they remain excluded until disarming of the same control panel.
If it is balanced at the end of the output time, when it is next balanced, the zone will be timed with the input time.
•
Key ON:
zone for remote arming in ON modality; therefore, the unbalancing of the zone in this way programmed will cause
the arming of the control panel in ON modality, activating the relative associated zones.
•
Key HOME:
zone for remote arming in HOME modality; therefore, the unbalancing of the zone in this way programmed will
cause the arming of the control panel in HOME modality, activating the relative associated zones.
•
Key AREA:
zone for remote arming in AREA modality; therefore, the unbalancing of the zone in this way programmed will
cause the arming of the control panel in AREA modality, activating the relative associated zones.
•
Key PERI :
zone for remote arming in PERIMETER modality; therefore, the unbalancing of the zone in this way programmed
will cause the arming of the control panel in PERIMETER modality, activating the relative associated zones.
•
24 Hours:
zone independent from arming of the control panel, active both with control panel disarmed and with control panel
armed; it can be excluded from the “ZONE OFF” function.
•
24H Delay (24 hour timed zone):
zone independent from arming of the control panel, active both with control panel disarmed
and with control panel armed. Upon its unbalancing, the return time is made available, signalled by an intermittent, highly
frequent, sound; upon expiry of this latter time an alarm activates, unless the user code has been in the mean time entered;
can be excluded from the function “ZONE OFF”.
CAUTION: The zones used as 24-hour timed are not compliant with EN50131 Grade 2
•
Tamper:
zone independent from arming of the control panel, activates both with control panel disarmed and with control
panel armed; it is used to connect the tamper proof and cannot be excluded from the “ZONE OFF” function
•
Fire:
zone independent from the switch-on of the central control unit, active with the control unit on or off, used to connect
fire sensors; can be used separate from the “ZONE OFF” function.
CAUTION: The areas used as FIRE are not compliant with EN50131-1 and EN 50131-3
•
Primary Fail:
zone independent from the switch-on of the central control unit, active with the control unit on or off; manages
the IMQ general siren failure signal.
•
Secondary Fail:
zone independent from the switch-on of the central control unit, active with the control unit on or off;
manages the IMQ general sensor failure signal
•
AntiMask:
(Anti Masking) zone independent from the switch-on of the central control unit, active with the control unit on or
off; manages the IMQ general anti masking sensor failure signal
•
Hold up:
zone independent from the switch-on of the central control unit, active with the control unit on or off, the alarm is
not displayed on the keypad; specific input for the anti-robbery devices.
CAUTION:
With the “Compliant with EN50131” option enabled, the “Encode Alarm” setting, if configured, refers to registration
of the event in the Event Memory only, while the other configurations remain active.
N.B.
The zones programmed as Key
(ON-HO-ZONE-PERI),
must be associated
to one partition only
N.B.
Zones from 9 to 32 are programmed by default as
[-] Unused
N.B.
The zones programmed as “24 hour zone” for the signalling of burglary, must not activate the alarm relay.
Press
(CLR)
to vary
Press
(ENT)
to confirm
Physical input
CPN n°x I.BA n°x
A
B
C
D
Physical input #
SAT 5 I.BA 3
to following
page
from previus