background image

- 28 -

RTC ACTIVATION BY A CALL FROM THE CONTROL PANEL

It is possible to activate the RTC function during an alarm telephone communication, by pressing 

key (7)

 after the two-tone signal. Subsequently, 

the control panel will reply - ENTER CODE -. Now follow the indications shown in the paragraph below.

USER RTC ACTIVATION

1. 

Compose, using a telephone in DTMF (multifrequency or “tones”), the telephone number where the control panel 

CAPTURE

 is installed.

2. 

Upon reaching of the number of “Reply Rings” set for PSTN calls and at first ring for GSM, a synthesized voice will say - ENTER CODE -.

• 

For calls through PSTN , 

if an 

answering machine

 is included, the overlapping can be activated

:

a.  Compose the telephone number and let it ring once.

b.  Put the receiver back and call again, 

at least after 8 seconds and not after 20 seconds from the first ring

.

c.  The control panel will reply at first ring, - ENTER CODE -, or, only on GSM channel, “ENTER COMMAND” if the recognition of incoming 

number procedure is enabled.

3. 

Slowly enter the User Code, which must be enabled for RTC functions; a synthesized voice will say - WELCOME TO THE REMOTE 

MANAGEMENT SYSTEM -; followed by - LIST AVAILABLE COMMANDS - 

4. 

The various functions can now be activated.

DTMF Commands

The commands are directly activated by pressing the keys on the telephone keypad. The DTMF commands described below are active or not, 

depending on the profile to which the user is associated.

ATTENTION:

 there is an interdiction time of two minutes between an RTC call and the subsequent one that doubles if the code inserted in the 

previous call is incorrect.

• 

[0] OFF ZONE: 

activates the possibility of excluding/including the input zones of the control panel from n. 1 to n. 32.

 

Example

[0] + (zone number) + (#)..

• 

[1] ESC:

 sector change.

• 

[2] MEM:

 listen to the events memory

• 

[3]

 

TEL OFF:

 causes the total loss of the telephone communication 

 

[4]

 

TEL OFF: 

causes the interruption of single telephone communication

• 

[5] OFF:

 causes the disarming of the control panel - CONTROL PANEL DISARMED -

• 

[6] O.C.:

 activates the possibility of controlling the Open Collector outputs from n. 1 to n. 250; activates only the 

O.C. programmed as “

O.C.User/Sect

” by users enabled to the function “

Enab. OC User

”. 

Example

: to control 

the O.C. n. 2; subsequently press keys [6] and [2] followed by 

[#]

 or 

[6] [0] [2]

.

• 

[7] TEST:

 supplies information on the state of the control panel.

• 

[9] ON:

 causes the arming of the control panel in modality ON - CONTROL PANEL ARMED ON -

• 

[#] ENTER:

 it is pressed to confirm a data introduced by the keypad.

• 

[

] STOP:

 it is pressed to interrupt a function (ex: the list of the events memory).

RTC USER with recognition of incoming number

This function enables the caller to communicate directly without having to enter the User code; active only for calls on GSM channel, therefore 

the XGSM or XGSM485 is necessary. This function happens only if during programming the telephone number from which the RTC operation is 

associated to a User enabled for RTC and to automatic “RTC validation”.

INSTALLER RTC ACTIVATION

• 

[0] RESET:

 Activates the deletion of all messages

• 

[1] REC:

 Activates recording

• 

[3] OFF TEL.:

 ends the telephone communication

• 

[5] PLAY:

 Plays the current message

• 

[4] <:

 Goes back by one or more recorded messages

• 

[6] >:

 Goes forward by one or more recorded messages

• 

[7] >:

 Enables reprogramming with XWIN through the GSM line of Central

• 

[#] ENTER:

 It is the confirmation command without which many of the other commands are not carried out

Summary of Contents for CAPTURE 16

Page 1: ...e foto cd dvd o altro materiale fornito dal cliente per l esecuzione del lavoro vanno richiesti alla consegna dopo la quale non si garantisce la restituzione Gli impianti stampa v possiamo garantire l...

Page 2: ...l features pag 21 SIM Card Inclusion Antenna Connector Input pag 21 XGSM485 XGSM485 PRO Technical features pag 22 Checking Credit and Expiry of the SIM Card for XGSM XGSM485 and XGSM485PRO pag 24 Reco...

Page 3: ...3 Q Extra power feeder in metallic box P Grado 2 POWER 5 Extra power feeder in board POWER 5 Q Extra power feeder in metallic box XMR2 2 relay board P Grado 3 MR4 4 relay board P Grado 3 MR8 8 relay...

Page 4: ...events can be memorised with date and time and outcome of the calls Alarm outputs n 1 alarm relay programmable with 2 ways and output Connect only circuits working with SELV voltage to these outputs...

Page 5: ...2 events can be memorised with date and time and outcome of the calls Alarm outputs n 1 alarm relay programmable with 2 ways and output Connect only circuits working with SELV voltage to these outputs...

Page 6: ...events can be memorised with date and time and outcome of the calls Alarm outputs n 1 alarm relay programmable with 2 ways and output Connect only circuits working with SELV voltage to these outputs...

Page 7: ...g up to the last satellite of the serial connection Example Central Control Unit Zones software zone 1 linked to terminal 1 of the central control unit base board software zone 8 linked to terminal 8...

Page 8: ...2 3 4 5 6 7 8 pre associated SOFTWARE ZONE 9 10 11 associated SOFTWARE ZONE O C SOFTWARE associato SATELLITE 02 C8 XSAT36 XSAT PW CLAMP BASIC Inputs Sat I BA xx EXTENSION Inputs Sat I EX xx 1 2 3 4 5...

Page 9: ...85 BASIC Inputs Sat M BA xx 1 2 3 4 5 6 7 8 pre associated SOFTWARE ZONE 25 26 27 associated SOFTWARE ZONE O C SOFTWARE associato SATELLITE 04 NO CAPTURE 8 C8 XSAT36 XSAT PW CLAMP BASIC Inputs Sat M B...

Page 10: ...A xx 1 2 3 4 5 6 7 8 pre associated SOFTWARE ZONE associated SOFTWARE ZONE O C SOFTWARE associato SATELLITE 06 NO CAPTURE 16 NO CAPTURE 8 C8 XSAT36 XSAT PW CLAMP BASIC Inputs Sat M BA xx EXTENSION Inp...

Page 11: ...1 2 3 4 5 6 7 8 pre associated SOFTWARE ZONE 25 26 27 associated SOFTWARE ZONE O C SOFTWARE associato SATELLITE 08 NO CAPTURE 16 NO CAPTURE 8 C8 XSAT36 XSAT PW CLAMP BASIC Inputs Sat M BA xx EXTENSION...

Page 12: ...uipment triggers a TAMPER alarm L6 L2 L1 L3 L4 L5 L7 L8 T R1 R1 R1 L6 This configuration allows only the alarm status of the zone corresponding with the unba lanced input to be recognised L1 L8 Negati...

Page 13: ...ammed as Inertial Vibration the central control unit signals the open zone if the connection cable is interrupted L2 L1 L3 L4 L5 L6 L7 L8 T These configurations permit direct management of Inertial or...

Page 14: ...eference for the input lines T input tamper C NC NO auxiliary output with exchange free from voltages positive safety with capacity 3 A 12 V C common exchange NC normally closed exchange NO normally o...

Page 15: ...nector J1 and EWEB or EWEB WIFI elettronic board on connector J3 making it slide inside the supports guides until it stops d Break the presetting on the control panel housing Left to form XGSM module...

Page 16: ...le is in the central control unit Technical Features 16 character 2 rows display screen Self updating micro flash T1 input with 4K7 resistance and negative reference T2 input is not used 20 Operationa...

Page 17: ...communications of the enabled events in menu Keypads A500 Settings Audio zones state set to YES to activate the communications of the associated inputs in menu Keypads A500 Settings Audio OC state set...

Page 18: ...an external sensor and similarly it is not possible to use the terminal as a zone input if programmed and physically connected to control a load with the OC output Please note that the tamper proof s...

Page 19: ...in HOME modality until the external state key completely disarms it Example 2 The control panel is armed in ON modality by an external state key Later the ZONE arming is controlled by keypad The cont...

Page 20: ...off the power to the control panel b Insert the vocal synthesis board on the control panel board introducing the connector place in front of the board lower face with the female J6 Memory Card placed...

Page 21: ...ssione 400 mA Electronic board sizes 93 x 15 x 60 mm Declaration The GSM modules used are compliant with R TTE Directive 99 05 EC as declared under the responsibility of the same manufacturer Time ala...

Page 22: ...number can not be defined since consumption during the ring phase varies from model to model XGSM485 and XGSM485 PRO TERMINAL BOARD ANT GSM Antenna cable plug connector BATT Output for battery connect...

Page 23: ...nd XGSM485 PRO External TAMPER between TO and negative with this connection opening of both the EXTERNAL TAMPER and the TAMPER BUTTON in the board are signalled Jumper S3 in position 2 3 External TAMP...

Page 24: ...Upon answering of the control panel enter the installer code and follow the vocal indications Should the PSTN telephone line not be available simulate it using a switchboard Procedure 1 Enable the PST...

Page 25: ...max 415 Iss All Rest YES Iss zone coding YES Iss telephone zone YES Iss zone num YES For every individual input it is possible to customise the communication by imposing the control panel to automati...

Page 26: ...33 B 103 EXECUTED 123 JUNE 201 PERIPHERICAL 35 BALCONY 97 EXHAUSTED 51 KEY 206 PLUS 36 BARRIER 241 EXPIRATION 71 KITCHEN 209 PORTER S_LODGE 249 BASEMENT 240 EXTENSION_BOARD 143 LABORATORY 210 POWER 34...

Page 27: ...M 295 THREE 168 WAY 144 SIDE 266 SYSTEM 269 THRESHOLD 164 WEDNESDAY 246 SIGNAL 278 TAMPER 122 THURSDAY 192 WEST 263 SIM 155 TAMPERING 294 TOTAL 111 WINDOW 264 SIREN 282 TAVERN 157 TUESDAY 95 WRONG 239...

Page 28: ...ZONE activates the possibility of excluding including the input zones of the control panel from n 1 to n 32 Example 0 zone number 1 ESC sector change 2 MEM listen to the events memory 3 TEL OFF cause...

Page 29: ...Example of INCORRECT sequences excl 12 arm on 2 zones state excl 12 arm on 2 zones state Only command answ and the SMS of state envision the sending of a reply message the others do not generate feedb...

Page 30: ...e alarm in progress belongs This is true for both the relay outputs and the Open Collector outputs Certain functions applicable to the Open Collector outputs require specifying the number of the secto...

Page 31: ...ses of the control panel WARNING Only one single Virtual XSATHP is supported in the configuration of the panel WARNING TheVirtualXSATHPfunctionCANNOTBEUSEDifusingphysicalXSATHPdevicesconnectedtothepan...

Page 32: ...ith regard to resetting the TAMPER Alarm Control Panel Label 16 alphanumerical string indicated when access to the programming menu Press CLR to vary To access other entries press or Write the number...

Page 33: ...ss CLR to vary To access other entries press or Writing keys 1 abc1 2 def2 3 ghi3 4 jkl4 5 mno5 6 pqr6 7 stu7 8 vwx8 9 yz 0 _ 0 Press arrows and to position the cursor Press ENT to confirm Operation T...

Page 34: ...associated zones Key HOME zone for remote arming in HOME modality therefore the unbalancing of the zone in this way programmed will cause the arming of the control panel in HOME modality activating t...

Page 35: ...l panel relay Sa S C NCNA Relay on satellite By setting YES the zone is enabled to activate the extension relay C NC NA Setting S establishes which relay must be activated Sirens active By setting YES...

Page 36: ...icated to the A500plus keypads enabled for communication of the zones state Disable detection survival Set at YES if wanting to deactivate the supervision control for the radio detector Disable detect...

Page 37: ...te During the AND time the zone can activate buzzer door chime pre alarm O C zone state O C alarm messages on keypad pre alarm events memory Tamper exclude If yes enables the simultaneous exclusion of...

Page 38: ...erial connection must be activated for the fire alarm Memo Fire Alarm By setting YES the Alarm Fire proof alarm will activate the Alarm Memorisation Memo Fire Reset By setting YES the Alarm Fire Reset...

Page 39: ...ng to the Partitions set at YES For the events of a single zone or a set of targeted zones it is necessary to leave everything at NO and to associate the O C with the single zones of reference Alarm i...

Page 40: ...sociated User Code is entered see User Profiles Fire it activates when there is a FIRE alarm coming from one of the satellites Reset Fire Activated when an enabled user performs a Reset Fire Line oper...

Page 41: ...m the control panel 255 disables this function Maintenance Interval months Time interval expressed in months that is reset every time one exits programming which upon expiry displays on the keypads th...

Page 42: ...User Codes User codes ENT The programmable User Codes are in total 128 and enable access to all management functions of the control panel The values by default are Ex User Code 1 000010 User Code 63...

Page 43: ...the associated TOYS within the period of time programmed in the Partitions menu N B The codes set at YES always work with double consent Chiave istantanea Si abilita i TOY abbinati al codice a lavorar...

Page 44: ...be enabled to disarm see Disarms control panel Disarms Timer arm disarms with timer active YES enables the Code to the disarming of the control panel even if the control panel has been previously arm...

Page 45: ...ction which number is herein programmed Emergency Channel Note if the emergency option is enabled YES the emergency code function will also be activated simultaneously with the operation associated wi...

Page 46: ...trol panel previously armed from Timer With a NO to disarm the control panel wait for the automatic disarming from Timer or disarm from keypad with a User Code enabled to disarm with Timer active CAUT...

Page 47: ...pad TOY selects the TOY memory locations to be programmed Acquisition TOY by accessing this menu the possibility of acquiring the Touch is activated Move the TOY towards the RS connector while the dis...

Page 48: ...keypad it is possible to enable the Quick Arm function for ON Macro key A and Macro key B Armed ON Setting to YES enables the QuickArm option for ON Utilizzando questa funzione decade la Conformit all...

Page 49: ...n of the Arming in ON modality HOMEArming Communication of the Arming in HOME modality AREA Arming Communication of the Arming in AREA modality PERI Arming Communication of the Arming in PERIMETER mod...

Page 50: ...eceived which detector has transmitted and to which control panel zone this is coupled For XSATHP satellites such as occurs sensors were acquired from which the satellite and the sensor type Satellite...

Page 51: ...e control panel or of one of the supervised power units connected in series drops below 10 5 V and there is no charging voltage It resets when voltage rises above 12 8 V Battery Unconnected with YES i...

Page 52: ...of the associated zones Unbalancing it activates with the unbalancing of at least one of the associated zones Tamper it activates with the tamper of at least one of the associated zones Antimask it a...

Page 53: ...urs and unblocks it after 24 hours from the first alarm Unlimited the siren does not perform any blocking Pricipal sound tone it is possible to select one of 8 tones for the Principal Sound Alternativ...

Page 54: ...rebalancing of the relative input 5 fast pulses the LEDs emit 5 quick flashes at the unbalancing of the relative input and de activated at the rebalancing of the relative input 1 pulse the LEDs are ac...

Page 55: ...interface towards which the calls are to be forwarded PSTN Select PSTN if wanting to forward calls only on analogical line GSM Select GSM if wanting to forward the call only on GSM channel using the...

Page 56: ...one communication User It is possible to associate the telephone number to a certain User to give the number the user features This association enables the called user to have the enablings dictated b...

Page 57: ...Partitons defined PATROL communicates the No entering of patrol code if it sets the manual rearming at YES to the associated number Us key false user false keys NO FAST Communication by a user or rea...

Page 58: ...we recommend setting a sufficient number of repetitions such to guarantee the recording of the message on the answering machine Num rings answer By enabling the Reply Rings function with a number of...

Page 59: ...ommunication with the central control unit in RS485 and any GSM anomalies to the first 8 telephone numbers programmed for communicating these events in GSM PSTN to XGSM485 When this function is enable...

Page 60: ...hould a rechargeable card be installed leave NO GPRS The parameters for data connection via XGSM are programmed in this menu APN Access Point Name Name of the access point server to which a mobile dev...

Page 61: ...included in SIA Coding is communicated in vocal or in the SMS Says zone speech communicates the telephone zone By setting YES the word ZONE is communicated in vocal or included in the SMS Says zone nu...

Page 62: ...e communications are sent and the relative port E G If the control panel does not dialogue via IP Addr A it automatically reroutes communications to IP Addr B and remains connected until a dialogue bl...

Page 63: ...unit Press CLR to vary Enter number to be set To access other entries press or Press ENT to confirm Dialler Enable NO A ENT B ENT IP Addr dev myavsalarm c Socket Port 27216 IP Addr dev2 myavsalarm c...

Page 64: ...time arming is delayed by 1 hour for a maximum of 3 times According to Standard CEI 79 2 the arming delay can be maximum of 180 minutes Disarms Active Timer By entering a Code enabled for the disarmin...

Page 65: ...ER STANDARD In this menu the alignment of the time of the control panel with the current time is programmed It is possible to activate that this function be automatic or set the parameters so that the...

Page 66: ...t peripherals such as EWEB EWEB WIFI Socket Port Access port for connection to PC via the proprietary AVS protocol E g for connection through ELM and XWIN the value of 2101 is usually configured Inst...

Page 67: ...mber or if in Telephone options Listen Reply is set at NO Press to move Press CLR to view information on the event like the string and result of telephone calls Press CLR to return to the displayed ev...

Page 68: ...atellite per monitorare i parametri dei satelliti Satellite ind selezionare il numero di satellite da monitorare Assorbimento mA indica il carico in mA complesYESvo collegato al satellite escluso la r...

Page 69: ...e is reset to default value 000000 ATTENTION By setting programming step R Def Prg Codes to YES the Code Reset sets all programming to default values Menu standby ENT Rem time min 60 Men standby By ac...

Page 70: ...S 2004 108 EC EMC 1999 05 EC R RTTE 2006 95 EC LVD E CHE SONO STATE APPLICATE LE SEGUENTI NORMATIVE APPLYING THE FOLLOWING NORMS OR STANDARDS EN 60950 1 2006 A11 2009 A1 2010 EN 50131 3 2009 1st Ed IE...

Page 71: ...71 Via Valsugana 63 35010 Padova ITALY Tel 049 9698 411 Fax 049 9698 407 avs avselectronics it www avselectronics com support avselectronics it...

Reviews: