Installing sneak current and off premise protection
Issue 3 January 2008
57
Installing sneak fuse panels
For general information, see
Installing sneak current and off premise protection
on page 54.
Figure 26: Model 507B sneak fuse panel
on page 55, or equivalent, is recommended for sneak
current protection. The panel contains two 25-pair connectors, fuse removal tool, and fifty
220029 sneak fuses (and two spares). See
Table 6: Sneak fuse connector pinout
on page 56
for pinout data.
To install sneak fuse panels:
1. Locate the 507B near the network interface or the main distribution frame (MDF).
2. Hold the panel against the mounting surface and mark the mounting screw locations. Drill
pilot holes at the marked locations and partially install a locally obtained #12 x 3/4-inch
screw into the two bottom mounting slots.
3. Slide the sneak fuse panel onto the mounting screws and tighten the screws securely.
4. Install a locally obtained #12 x 3/4-inch screw into the top two mounting slots and tighten
securely.
5. Repeat the procedure for each sneak fuse panel.
6. Secure the B25A cable to the panel with the captive screw on the connector and a supplied
cable tie.
45/20
20
46/21
21
47/22
22
48/23
23
49/34
24
50/25
25
Table 6: Sneak fuse connector pinout (continued)
Connector
pin numbers
Pair/fuse
number
2 of 2
Summary of Contents for 03-300686
Page 1: ...Installing and Connecting the MDF and Telephones 03 300686 Issue 3 Release 5 0 January 2008 ...
Page 8: ...Contents 8 Installing and Connecting the MDF and Telephones ...
Page 28: ...Installing the main distribution frame 28 Installing and Connecting the MDF and Telephones ...
Page 32: ...Installing the patch panel 32 Installing and Connecting the MDF and Telephones ...
Page 40: ...Media gateway connections to the MDF 40 Installing and Connecting the MDF and Telephones ...
Page 53: ...Completing a provisioning plan Issue 3 January 2008 53 Figure 25 Port Assignment Record Form ...
Page 156: ...156 Installing and Connecting the MDF and Telephones Index ...