1151B1 and 1151B2 Power Supplies
Issue 3 January 2008
133
!
CAUTION:
CAUTION:
The power supply can be used
only
with telecommunications equipment, indoors,
and in a controlled environment.
The power supply has a single output of -48 VDC, 0.4 amperes and can operate from either a
120 VAC 60 hertz power source (105 to 129 VAC) or a 220/230/240 VAC 50 hertz power source
(198 to 264 VAC). Input voltage selection is automatic. The output capacity is 19.2 watts.
The power supply can be placed on a flat surface such as a desk. For wall-mounting, keyhole
slots are provided on the bottom of the chassis.
!
CAUTION:
CAUTION:
Do not locate the unit within 6 inches (15 centimeters) of the floor.
Connecting the 1151B1 or 1151B2 Power Supplies
The 1151B1 is a standard (no battery backup) power supply unit. The 1151B2 is a battery
backup version of the 1151B1. Either power supply can support one telephone with or without
an adjunct. The maximum loop range is 250 feet (76 meters). Two modular jacks are used.
Power is provided on the PHONE jack, pins 7 and 8 (- and +, respectively).
The PHONE and LINE jacks are 8-pin female nonkeyed 657-type jacks that can accept D4, D6,
and D8 modular plug cables. See an
Figure 59: 1151B2 Power Supply — front
on page 133.
Figure 59: 1151B2 Power Supply — front
pwr_sup1 CJL 051496
Summary of Contents for 03-300686
Page 1: ...Installing and Connecting the MDF and Telephones 03 300686 Issue 3 Release 5 0 January 2008 ...
Page 8: ...Contents 8 Installing and Connecting the MDF and Telephones ...
Page 28: ...Installing the main distribution frame 28 Installing and Connecting the MDF and Telephones ...
Page 32: ...Installing the patch panel 32 Installing and Connecting the MDF and Telephones ...
Page 40: ...Media gateway connections to the MDF 40 Installing and Connecting the MDF and Telephones ...
Page 53: ...Completing a provisioning plan Issue 3 January 2008 53 Figure 25 Port Assignment Record Form ...
Page 156: ...156 Installing and Connecting the MDF and Telephones Index ...