2.3 Environmental
Temperature Coefficient
Voltage Set Point: 0.02%/C of V Range
Current Set Point: 0.03%/C of I Range
Ambient Temperature
Operating: 0° to 40° C / 32° to 104° F
Storage: -40° to 75° C /-40° to 167° F
Humidity:
0 to 80 % RH, non condensing
Cooling:
Forced Air. Front, side and top air intake, rear exhaust.
Altitude
Operating: 2000 meters max.
Storage: 6000 meters max.
2.4 Mechanical
Dimensions:
Width:
19.00 “/ 482.6 mm
Depth:
22.19”/ 563.3 mm
(excluding bus bars and cover)
Height: 5.25”/133.35
mm
Unit Weight:
15 kW model: Net: 90 Lbs. / 40.8 Kg.
Gross: 125 Lbs. / 56.7 Kg
10 kW model: Net: 70 Lbs. / 31.8 Kg.
Gross: 105 Lbs. / 47.6 Kg
5 kW model:
Net: 50 Lbs. / 22.7 Kg.
Gross: 85 Lbs. / 38.6 Kg
Material: Chassis:
Steel.
(Anodized)
Top cover:
Aluminum (Anodized)
Front panel
Aluminum (Anodized)
Cooling:
Forced air, side and top intake, rear exhaust
Acoustic Noise Level:
(Measured at 1 meter
from front of unit).
5 KW: < 55 dBA
10KW: < 60 dBA
15KW: < 65 dBA
Internal Construction:
Modular construction.
Rear Panel
Connections:
AC Power Input, DC power out, RS232, GPIB (option), Analog
Programming (option)
Rack Mounting
Unit must be supported by shelf or brackets when mounted in 19"
cabinet.
No provisions for rack slides are made on instrument.
Summary of Contents for XDS 100-100
Page 4: ...User and Programming Manual 4 XDS Series Electrical Safety Symbols Used in This Manual ...
Page 27: ...User and Programming Manual XDS Series 27 Figure 3 5 Outline Drawing XDS DC Supply ...
Page 41: ...User and Programming Manual XDS Series 41 Figure 5 4 Parallel Cable Interconnect Accessory ...
Page 69: ...User and Programming Manual XDS Series 69 Figure 8 3 Replaceable Fuse Locations ...