Reset time
<50 ms
No
Notte!
e!
• The minimum voltage for the power factor calculation is 1.0 V secondary and the minimum
current is 0.1 A secondary.
9.2.1.20 Volts-per-hertz overexcitation protection (V/Hz>; 24)
Table. 9.2.1.20 - 328. Technical data for the volts-per-hertz overexcitation protection function.
Measurement inputs
Voltage input
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
Voltage input magnitude
Maximum line-to-line voltage
Frequency reference 1
Frequency reference 2
Frequency reference 3
CT1IL1, CT2IL1, VT1U1, VT2U1
CT1IL2, CT2IL2, VT1U2, VT2U2
CT1IL3, CT2IL3, VT1U3, VT2U3
Pick-up
Pick-up setting
0.01…75.00 %, setting step 0.01 %
Inaccuracy:
- V/Hz
±1.0 %
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (VHZ
M
/VHZ
SET
ratio 1.05)
±1.0 % or ±25 ms
Instant operation time
Start time and instant operation time (trip):
- VHZ
M
/VHZ
SET
ratio 1.05)
<40 ms
Reset
Reset ratio
97 % of the pick-up setting
Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±25 ms
Instant reset time and start-up reset
<40 ms
No
Notte!
e!
• Mea
Measur
surement
ement: Volts-per-hertz protection checks the highest line-to-line voltage. The used
sampling mode for frequency must be "Tracking".
9.2.1.21 Underexcitation protection (Q<; 40)
Table. 9.2.1.21 - 329. Technical data for the underexcitation protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
+ U
0
Calclucated measurements
Three-phase reactive power
Pick-up
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
445