Name
Range
Step
Default
Description
Language
0: User defined
1: English
2: Finnish
3: Swedish
4: Spanish
5: French
6: German
7: Russian
8: Ukraine
-
1: English
Changes the language of the parameter descriptions in
the HMI. If the language has been set to "Other" in the
settings of the AQtivate setting tool, AQtivate follows the
value set into this parameter.
UTC time
-
-
-
Displays the UTC time used by the unit without time
zone corrections.
Clear events
0: -
1: Clear
-
0: -
Clears the event history recorded in the AQ-200 device.
LCD Contrast
0…255
1
120
Changes the contrast of the LCD display.
Return to default view
0…3600 s
10 s
0 s
If the user navigates to a menu and gives no input after
a period of time defined with this parameter, the unit
automatically returns to the default view. If set to 0 s, this
feature is not in use.
LED test
0: -
1: Activated
-
0: -
When activated, all LEDs are lit up. LEDs with multiple
possible colors blink each color.
Reset latches
0: -
1: Reset
-
0: -
Resets the latched signals in the logic and the matrix.
When a reset command is given, the parameter
automatically returns back to "-".
Measurement recorder 0: Disabled
1: Enabled
-
0: Disabled
Enables the measurement recorder tool, further
configured in
Tools
→
Misc
→
Measurement recorder.
Reconfigure mimic
0: -
1: Reconfigure
-
0: -
Reloads the mimic to the unit.
Reset last fault
registers
-
-
-
Activation of input selected here resets the values in
"Fault registers" view in carousel.
Protection/Control/
Monitor profile
-
-
-
Displays the status of all enabled functions.
Function comments
Function comments displays notes of each function that has been activated in the Protection, Control
and Monitoring menu. Function notes can be edited by the user.
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
16