Frequency
±15 mHz (U > 30 V secondary)
±20 mHz (I > 30 % of rated secondary)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio +/- 50 mHz)
±1.5 % or ±110 ms (max. step size: 100 mHz)
Start time and instant operation time (trip):
f
M
/f
SET
ratio +/- 20 mHz (overreach)
<180 ms
f
M
/f
SET
ratio +/- 200 mHz (overreach)
<90 ms
Reset
Reset ratio (frequency limit)
0.020 Hz
Instant reset time and start-up reset
- f
M
/f
SET
ratio +/- 50 mHz
<2 cycles or <60 ms (max. step size: 100 mHz)
No
Notte!
e!
• The frequency is measured two seconds after a signal is received.
9.2.1.13 Machine thermal overload protection (TM>; 49M)
Table. 9.2.1.13 - 321. Technical data for the machine thermal overload protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
TRMS phase currents (up to the 31
st
harmonic)
Pick-up (Heating)
NPS bias factor (unbalance effect)
Pick-up current setting
Thermal alarm and trip level setting range
Motor service factor
0.1…10.0, setting step 0.1
0.10…40.00 × I
N
, setting step 0.01 × I
N
0.0…150.0 %, setting step 0.1 %
0.01…5.00 × I
N
, setting step 0.01 × I
N
Cold condition:
- Long heat T const (cold)
- Short heat T const (cold)
0.0…500.0 min, setting step 0.1 min
0.0…500.0 min, setting step 0.1 min
Hot condition:
- Long heat T const (hot)
- Short heat T const (hot)
- Hot condition theta limit (Cold
→
Hot spot)
0.0…500.0 min, setting step 0.1 min
0.0…500.0 min, setting step 0.1 min
0.00…100.00 %, setting step 0.01 %
Reset (Cooling)
Reset ratio (pick-up and alarms)
99 %
Stop condition:
- Long cool T const (stop)
- Short cool T const (stop)
- Short cool T in use time
0.0…500.0 min, setting step 0.1 min
0.0…500.0 min, setting step 0.1 min
0.0…3000.0 min, setting step 0.1 min
Run condition:
- Long cool T const (stop)
0.0…500.0 min, setting step 0.1 min
Operation time
Definite time function operating time setting
0.0…3600.0 s, setting step 0.1 s
Inaccuracy:
- Pick-up and reset
±1.0 % or ±500 ms
Environmental settings
A
AQ
Q-G215
-G215
Instruction manual