Thermal replica temperature estimates
Selectable between °C and °F
Ambient temperature effect
k min. and max. range
Ambient temperature min. and max. range
Linear or manually set curve
0.01...5.00 × I
N
, setting step 0.01 × I
N
–60…500 deg, setting step 1 deg
Thermal model biasing (ambient):
- Set ambient temperature
- RTD
–60…500 deg, setting step 1 deg
Used measured ambient value
9.2.1.14 Power protection (P, Q, S>/<; 32)
Table. 9.2.1.14 - 322. Technical data for the power protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
(+ U
0
)
Calculated measurements
Three-phase active, reactive or apparent power (P, Q or S) value based on the chosen or
set nominal amplitude.
Pick-up
Comparator selection
> or <
> or <
-500.000...500.000 %/MVA
N
, setting step 0.005 %/MVA
N
Inaccuracy:
- Active, reactive, or apparent
power
Typically <1.0 %P
SET
Operation time
Definite time function operating
time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (P
M
/P
SET
ratio
1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation
time (trip):
- PQS
M
/PQS
SET
ratio 1.05
→
<40 ms
Reset
Reset ratio
97 or 103 %P
SET
Instant reset time and start-up
reset
<40 ms
No
Notte!
e!
• The voltage measurement starts from 0.5 V and the current measurement from 25 mA. In
case either or both are missing, the measured magnitude is forced to 0 MW/MVar/MVA.
Please avoid using settings that should operate below the relay's current squelch limit (25 mA
on the relay terminal).
• With very small under power pick-up settings time delay inaccuracy might double.