-LKS
Clock and Lock Auxiliary. See -LKM for details. (see Notes) See section
3.9.
-LNS
Line Sync (see Notes)
-EXS
External Sync (see Notes)
-RMS
Set of 2 Rack mount slides. (Left and Right) Recommended to mount CS
Chassis in 19 inch instrument cabinet.
Notes:
External Trigger input is standard.
Line sync and External sync are mutually exclusive.
External Trigger input and External sync are mutually exclusive.
Units with -LKS (auxiliary) cannot have Line Sync or External Sync.
-RPV
Remote programming voltage. DC voltage input 0 to 10 VDC for 0 to full-
scale output voltage programming.
2.6.1
-AX Option CS Series - Supplemental Specifications
Specifications for -AX auxiliary output voltage option on the CS units are listed below. This
output is available on the Phase D and E terminal strip. There is no external sense connection
for the –AX outputs. Sense is internal only. Specifications apply for programmed frequency
range of 360 Hz to 440 Hz.
Parameter
Supplemental Specification
Phase D Output
Voltage 26.0 Vrms ± 0.52 V
Load Regulation < 1.5 %
Voltage Distortion < 1.0 % THD
Max. Current 3.0 Arms
Frequency range: 360 – 440 Hz, locked to programmed frequency.
If programmed exceeds 819 Hz, -AX outputs will turn off.
Phase error to phase 1 < 3.0°
Phase E Output
Voltage 5.0 Vrms ± 0.25 V
Load Regulation < 10 %
Max. Current 1.0 Arms
Frequency range: 360 – 440 Hz, locked to programmed frequency.
If programmed exceeds 819 Hz, -AX outputs will turn off.
Phase error to phase 1 < 3.0°