2. Specifications
Specifications shown are valid over an ambient temperature range of 25
±
5
°
C and apply after a
30 minute warm-up time. Unless otherwise noted, all specifications are per phase for sine wave
output into a resistive load. For three phase configurations or mode of operation, all
specifications are for Line to Neutral (L-N) and phase angle specifications are valid under
balanced load conditions only.
2.1 Electrical
2.1.1 Input
Parameter
Specification
Line Voltage:
(3 phase, 3 wire
+ ground (PE))
3000CS, 4500CS, 9000CS/2, 13500CS/3,
18000CS/4:
Std:
208 - 230 VLL ± 10%
-400: 400
V
LL
±
10%
Note: Each CS chassis requires its
own AC service.
Note: 3000CS may be operated
from 208-230 V L-N single phase
AC input between B and C on TB3
for 3000CS.
Line VA:
(total)
3000CS
5900 VA / 4100 W
4500CS
8900 VA / 5900 W (x2 for 9000CS/2, x3 for 13500CS/3, x4
for 18000CS/4)
Line Current:
(per phase)
3000CS
Std: 19 Arms @ 187 VLL, 3 phase AC input.
[32 Arms @ 187 VLN single phase AC input. Connect
between TB3-B and TB3-C]
-400: 10 Arms @ 360 VLL, 3 phase AC input.
4500CS
Std: 31 Arms @ 187 VLL
-400: 16 Arms @ 360 VLL
Currents shown are for single chassis models. For multi-chassis
configurations, currents are per chassis.
Line Frequency:
47-440 Hz
Efficiency:
75 % (typical) depending on line and load
Power Factor:
0.65 (typical)
Inrush Current:
50 Apk @ 253VLL per chassis
83 A
pk
@ 400
V
LL
per chassis
Note: Each CS chassis requires
its own AC service.
Hold-Up Time:
> 10 ms
Isolation
Voltage:
2200 VAC input to chassis and input to output.