![Alstom SHPM 101 Service Manual Download Page 85](http://html1.mh-extra.com/html/alstom/shpm-101/shpm-101_service-manual_2908927085.webp)
SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 2
Page 23 of 74
registers are designated timer run out registers (TROR) and contain the timer run
out bits.
The timer start bit is set in the main loop when the timer is required to run.
Similarly this bit is set when the timer is to be reset. When the appropriate timer is
serviced by the timer interrupt, the timer start bit will be tested to see if the timer is
to be run. If a run condition is required then the timer will perform a counting
sequence in a register that has been designated a timer register.
The count within this register is incremented every time the timer is serviced by the
timer interrupt routine (every 1.974ms). When the timer has reached the required
count, the timer routine sets a bit in the timer run out register, this is the timer run
out bit. Every time the program executes the main loop the timer run out bit will be
tested to see if the timer has finished. If a reset condition is required, the timer run
out bit and the timer register are reset when the timer is next serviced by the
interrupt routine. Thus the timer is ready to be run when required. A list of all the
interrupt timers is given in Table 4.
Each of the 16 timers is allocated at least one timer register; long timers such as
the VTS 5.5s timer require more than one timer register.
The settable Zone 2 and Zone 3 delayed trip timers use multiples of a basic timer
length (eg. Z2 basic length is 10ms). The appropriate switches are used to provide
the multiplication factor. There is a 17th interrupt timer which is used to generate
the 2 week automatic self check delay.
4.9.45 Loop timers
Several of the shorter timers used within the scheme logic are loop timers.
These timers are run completely within the main loop. The operating principle of
these timers is described below.
When the timer is required to run, a register which is designated a timer register is
incremented once every time the main loop is executed. This is then tested to
determine if the timer has finished, if it has, then the timer register is reset. A list of
all the loop timers is given in Table 5.
TIMER FUNCTION
TIMER LENGTH
TIMER RESOLUTION
SIGNAL RECEIVE DROP OFF
100ms
td
0 – 90ms
6ms
tp
0 – 90ms
6ms
BLOCK AUTO
100ms
–
RECLOSE DROP OFF
ANY POLE DEAD
240ms
–
DROP OFF
VTS ACCELERATED
20ms
–
INDICATION PICK UP
SYNCHRONOUS
140ms
–
POLARISING (MEMORY)
ENABLE PICK UP
(POR) CIRCUIT BREAKER
60ms
–
OPEN PICK UP
SOTF DEAD TIME
200ms or 110s
–
SOTF ENABLE TIME
240ms
–
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......