SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 5
Page 23 of 24
In this case it can also be seen that operation would be obtained by reversing
the current and voltage rotation need not be carried out.
To enable any load condition to be understood Figure 11C provides the facility
for drawing the characteristic.
If the load vector is near the directional characteristic boundary, eg. an RCA of
85
°
and a load power factor of unity or slightly leading, then the load test may
not appear conclusive as some phases may not operate.
This may be made more conclusive by lowering the RCA temporarily by means
of ØPh.
An alternative method of making the directional check conclusive for a similar
condition is by rotating the voltage vectors through 120
°
by means of a heavy
duty test plug inserted in the 1Z position as shown in Figure 9B.
If voltage rotation is necessary it is best to select
∞
on K11 after inserting the
test plug with the rotation connections on it.
iii) A check must also be made to ensure that operation does not occur in the
reverse direction. This is achieved by inserting a test plug in the 1Y position with
links already on it, as shown in Figure 9A.
iv) After the test has been completed ensure that K11 is on its correct setting. If any
other switches have been used to assist the test ie. K1, K2 or Ø
Ph
make sure
they also are put back to their correct settings. Insert the normal 1Y and 1Z
bridging plugs.
Note:
The directional characteristic may not be a perfect straight line and if a
near boundary operation occurs in the reverse direction, the normal
angular hysteresis will operate in the wrong direction until the memory has
run out. If Ø
Ph
is lowered by 10
°
the effect should disappear and no
operation be obtained.
If a self-check is done with K11 in the
∞
position without the outgoing contacts
inhibited, the relay may indicate that it is not available. When K11 is returned
to its normal position and another self-check is done on the comparators, then
relay available indications will be restored.
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......