SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 2
Page 5 of 74
The time delay of 26 to 36ms between fault inception and signal transfer is
sufficient to allow fast tripping to occur, if electrical conditions permit, before the
intervention of the filters. If fast tripping does not occur, the 26 to 36ms delay is
long enough for the transient errors of the band pass filters, caused by the
collapsing voltage, to have decayed away before signal transfer to the band pass
outputs.
At the instant of switching in the band pass filters, a step in the voltage waveform
may arise and to ensure that this causes no confusion to the comparators a
momentary inhibit pulse is sent to all the comparators. The voltage supply is
switched back to normal when (a) the fault is removed by a remote breaker so that
the voltage is restored to normal and the voltage level detectors pick up again, (b)
when the fault is cleared by de-energising the line such that one or more pole-dead
level detectors operate. This control logic is performed by software in the scheme
logic module (see Section 5.16.18 and Figure 66).
When the relay trips the circuit breaker, a logic signal is sent from the scheme
logic module to the input labelled “TRIP” to instruct the relay reach to be increased
by 5% by reducing the gain of the voltage buffer amplifiers, which produce outputs
V
A
, V
B
and V
C
, by 5%. This hysterisis control defines the reset ratio of the relay and
prevents chatter of relay output contacts for faults on the boundary of operation
(see Section 5.16.19).
The outputs V
A
, V
B
and V
C
are buffered by operational amplifiers which produce
outputs V
A
', V
B
'
and V
C
' respectively.
The C phase output from the band pass filter is buffered to drive the memory
facility of the relay, see Section 4.9.17, on output V
mem
.
The overall transfer functions for the voltage input module with healthy line
conditions at the nominal power system frequencies are:
Vout = 0.066304 /–10
°
(50Hz models)
Vin
Vout = 0.065854 /–12
°
(60Hz models)
Vin
4.3
The current input module RFC 15
This module receives current from the line current transformers on inputs
I
A
,
I
B
,
I
C
and
I
N
via the heavy duty plug bridge piece 1Y on the side of the module and
produces the replica impedance signals
I
A
1
and
I
A
2,
I
B
1 and
I
B
2,
I
C
1
and
I
C
2,
I
N
1,
I
N
2
and
I
N
3
(see Block Diagram Figure 7).
Replica impedance signals are generated by the mixing of magnetic fluxes in the
transphasor units, as described in detail in Section 5.14. Each transphasor
arrangement produces an output voltage of 0.34 V/A (1A relay) across a 5k
Ω
load located in the phase and neutral module. The residual compensation
arrangement produces an extra output on
I
N
1–
I
N
2
of 0.068 V/A (1A relay)
across a 1k
Ω
load, also located in the phase and neutral module. Each output is
calibrated at the factory by use of the trimpot T.
The replica phase angles are set by switches “/
θ
Ph” and “/
θ
N” on the relay facia
(see Figure 8) which have a setting range of 45
°
to 85
°
in 5
°
steps. These switches
control the variable resistors shown in Figure 7. The angle setting for currents
I
A
,
I
B
and
I
C
are ganged.
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......