SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 2
Page 53 of 74
single phase to ground faults, with 3 phase tripping for other faults, or 3 phase
tripping for all faults is also provided.
To set up the relay for a particular scheme option requires the correct code
selection number (CSN) to be set on the code switches, which are positioned on
the frontplate of the scheme logic module. Details are given in Table 8.
CSN
Scheme
Comments
(XY)
00
BASIC with single phase/3 phase tripping
Provides basic
Zone 1
Z2t, Z3t and
SOTF action
01
BASIC with 3 phase tripping only
Basic action as per 00
02
PUR with single phase/3 phase tripping
Includes basic
action
03
PUR with 3 phase tripping only
04
POR with single phase/3 phase tripping
05
POR with 3 phase tripping only
06
BLOCK with single phase/3 phase tripping
Includes basic action
07
BLOCK with 3 phase tripping only
08
Z1EXT with single phase/3 phase tripping
09
Z1EXT with 3 phase tripping only
Table 8: The standard scheme options
The first digit of the CSN is the left switch labelled “X” on the relay nameplate,
while the second digit is the switch labelled “Y”. The range of code selection
numbers available for scheme options is in the range 00 to 39. Positions 40 to 99
are for test options (see Sections 6.42 and 4.54). If a CSN is selected in the range
00 to 39 which does not have a scheme allocated to it, the “Relay Available” LED
is extinguished and the output contact “Relay Inoperative” (97Y–1) closes.
5.16.23 Basic scheme
This scheme controls the normal Zone 1 action, the Zone 2 and Zone 3 time
delayed trip action and the SOTF trip action. The time delays associated with Zone
2 faults (Z2t) and those for Zone 3 faults (Z3t) are set by switches on the frontplate
of the scheme logic module.
5.16.24 Permissive underreaching scheme (PUR)
The underreaching directional Zone 1 elements are used to initiate tripping and to
send a signal (85X–1 and 85X–2) to the remote end of the transmission feeder.
Operation of the overreaching Zone 2 elements plus receipt of the channel signal
(via opto isolator input CRX), gives an accelerated trip for faults occurring in the
end zones of the protected feeder. Once issued, the aided trip is only removed
when the Zone 2 elements reset. This is to allow time for breaker failure protection
operation in the event of a local breaker failure for a fault near the remote end of
the line. A delay on reset of the signal received (CRX), is needed to ensure that the
relays at both ends of a single end, fed faulted line of a parallel feeder circuit have
time to trip when the fault is close up at one end. A preset 100ms is used for this
delay. Figure 68 gives the equivalent logic diagram.
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......