SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 2
Page 70 of 74
6.13
Operating and reset times
Minimum
(50HZ)
14ms
(60Hz)
13ms
Mho characteristic
Typical
(50Hz)
18–25ms
(60Hz)
16–23ms
Minimum
(50HZ)
19ms
(60Hz)
17ms
Mho characteristic
Typical
(50Hz)
25–33ms
(60Hz)
22–29ms
These times include the operating times of the electro-mechanical tripping output
relays.
The maximum reset time is 36ms with the proviso that the main trip contacts
(Trip A, Trip B, Trip C, Trip 3Ph and Any Trip) are sealed in for a minimum period
of 60ms following the initial trip.
6.14
Voltage transformer (fuse failure) supervision
The voltage transformer supervision operates when zero sequence voltage is
detected without the presence of zero sequence current. This does not limit the
current sensitivity of the distance measuring elements.
Nominal V
0
detector setting 9.5V (15% V
n
).
Blocking action of distance comparators can be removed by switch SW3.
When miniature circuit breakers are used the comparators are blocked when the
MCB opens regardless of the position of SW3.
6.15
Power swing blocking
Power swing blocking zone (Zone 6) has mho or lenticular characteristic.
Aspect ratio of the lens is the same as that of Zone 3. Power swing blocking may
be enabled/disabled by SW9.
Settings:
Zone 6 forward = Zone 3 f 0.3 x Zone 3 forward
Zone 6 reverse
= Zone 3 r 0.3 x Zone 3 forward
Timer
= 50ms
Blocking:
Individual blocking of Zone 1 and/or Zone 2 and/or Zone 3 with
indication/alarm or indication/alarm only as selected by switches
on the scheme logic module. Blocking is removed if a ground fault
occurs during a power swing.
6.16
Operative ambient temperature range
The operature ambient temperature range is –25
°
to 55
°
C.
6.17
Operative frequency range
The operative freqency range is:
47 to 51Hz
(f
n
= 50Hz)
56.4 to 61.2Hz
(f
n
= 60Hz)
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......