SERVICE MANUAL
R5888B
QUADRAMHO
Chapter 1
Page 10 of 27
A has ceased to transmit a signal. It may be that end B will cease to receive a
signal before its Zone 2 element picks up, in which case there would not be a fast
trip. It is therefore necessary to have a delay on reset of the signal received, so
that in the case above, end B will be allowed to fast trip when its Zone 2 element
picks up.
Time delay t = 100ms
Refer to Figure 68, Chapter 2 for block diagram of permissive underreach scheme.
18.2
Permissive overreach scheme
Operating conditions:
Zone 1 operation – –> instantaneous trip
Zone 2 operation – –> signal send
Zone 2 ope signal receive – –> instantaneous trip
CURRENT REVERSAL AFTER NEAREST CB OPENS
The current reversal guard incorporated in the scheme logic is initiated when a
healthy circuit relay receives a permissive trip signal, but does not have a Zone 2
element picked up. A delay on pick up (tp) of the current reversal guard is
necessary in order to allow time for Zone 2 elements to pick up, if they are going
to time, for an internal fault.
Recommended setting tp = 30ms – signalling channel P/U time
(or nearest setting above this value)
Once the current reversal guard has picked up (healthy circuit relay at end A),
transfer tripping is inhibited. The reset of the guard is initiated by either the loss of
permissive trip signal or by the pick up of a Zone 2 element. A time delay (t
D
) for
the reset of the reversal guard, is required in case the Zone 2 element (end A)
picks up before the permissive trip signal from the other relay (end B) has reset
which could cause healthy circuit tripping.
Recommended setting t
D
= signalling channel D/O time + 25ms
(or nearest setting above this value)
Refer to Figures 69 and 70, Chapter 2, for block diagram of permissive overreach
scheme.
A
Open
B
A
B
a) Fault occurs
b) End A relay trips
Strong
Strong
Weak
Weak
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......