![Alstom SHPM 101 Service Manual Download Page 294](http://html1.mh-extra.com/html/alstom/shpm-101/shpm-101_service-manual_2908927294.webp)
SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 6
Page 6 of 12
and for reverse reach ground faults is:
(K1 + K2 + K4 + K5 + K6) (K35 + K36) K33 x K37
ohms
I
n
The phase fault loop impedances required are for forward faults:
2 x (K1 + K2) (K31 + K32) K33
ohms
I
n
and for reverse phase faults:
2 x (K1 + K2) (K35 + K36) K33 x K37
ohms
I
n
The reach checks should be carried out for each element of the relay as in
Section 4.5.1.
Note:
For the reverse reach an additional tolerance of
±
15% is allowed.
4.6
Check Z3 lenticular polar plot (lenticular versions only).
To check the lenticular shape, note the relay settings and return to them after
this test.
Set a/b = 0.41 and the forward and reverse reaches to the same, ie.
(K31 + K32) K33 = (K35 + K36) (K37 + K33)
Also set ØPh = ØN = 80
°
Figure 6 shows the normalised theoretical shape for Zone 3 for these conditions.
From this diagram the theoretical reach ZT, for off angle faults can be determined
for both forward and reverse faults. Using this information the ground fault loop
impedance required is:
(K1 + K2 + K4 + K5 + K6) (K31 + K32) K33 x ZT
ohms
I
n
at the particular angle of ZT.
The phase fault loop impedance required is:
2 x (K1 + K2) (K31 + K32) K33 x ZT ohms
Check the reach as in Section 4.5 allowing the same tolerances.
4.7
Resistive reach check (if quadrilateral characteristic is fitted)
Checks are done using resistive faults, thus in the forward direction all zones will
be seen to operate at the same loop impedance.
The required loop fault resistance is:
K3
ohms
I
n
When the fault is reversed, only Zone 3 should operate due to the slope on the
bottom line of the characteristic for Zones 1 and 2.
The checks should be carried out for all phase to ground faults and results should
be within
±
10% of the selected setting.
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......