SERVICE MANUAL
R5888B
QUADRAMHO
Chapter 1
Page 9 of 27
• For standard POR schemes, fast clearance will not occur for all faults along the
protected line section if there is weak or no infeed at one terminal. It is possible
with Quadramho to switch in a weak infeed feature which will allow aided
tripping of the strong infeed relay and three phase tripping of the weak infeed
relay. The feature used undervoltage logic and Zone 3 elements set to be
reverse looking.
17.5
Blocking (see Figure 8)
This scheme requires only one signalling channel for both relays.
Two forward zones of protection are available, as Zone 3 elements are required to
be reverse looking, for initiating blocking signal.
This scheme will provide similar resistive fault coverage to POR.
If a line terminal is open, fast tripping will still occur for faults along the whole of
the protected line length.
If the signalling channel fails, fast tripping will occur for faults along the whole of
the protected line, but also for some faults within the next line section.
Fast tripping will still occur at a strong source line terminal, for faults along the
protected line section, if there is weak or no infeed at the other terminal.
Section 18.
TIMER SETTINGS FOR DISTANCE SCHEME LOGIC OF QUADRAMHO
18.1
Permissive underreach scheme
Operating conditions:
Zone 1 operation – –> instantaneous trip + signal transmit
Zone 2 ope signal receive – –> instantaneous trip
Special aspects to consider:
SINGLE END FED DOUBLE CCT LINE, FAULT CLOSE UP
In the situation outlined above, end B receives a permissive trip signal from the
faulted circuit relay at end A. A trip cannot occur at end B however, because it
sees negligible fault current. When end A trips, end B sees a Zone 2 fault, but end
A
Open
B
A
B
a) Fault occurs – busbar voltage
low so negligible fault current
via end B.
b) End A relay clears fault and
current starts feeding from
end B.
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......