SERVICE MANUAL
R5888B
QUADRAMHO
Chapter 1
Page 17 of 27
Select
K4
= 1
K5
= 0.4
K6
= 0.00
θ
N
≥
/KN.Z
Ph
θ
N
≥
67.3
°
Select
θ
N
= 70
°
Actual Z
N
= 0.28 /70
°
ohms
Coarse ground loop impedance = Z
Ph
+ Z
N
= 0.28 /70
°
+ 0.28 /70
°
= 0.56 /70
°
ohms
19.8
Setting restrictive reach of ground fault comparators
Required primary resistive coverage for ground faults = 40 ohms
40 ohms primary = 2.92 ohms secondary
Minimum load impedance likely to be seen by ground fault distance comparators
=
60 x 10
3
3 x 200
= 173 ohms primary
=12.6 ohms secondary
There will, therefore, be no problems of load encroachment on the ground fault
comparator operating regions, if the comparators are set to see 40 ohms primary
fault resistance.
Select nearest resistive reach setting above that required.
R
S
=
K3 = K3 = 2.92 ohms
I
n
5
Select K3 = 16
Actual resistive reach = 3.2 ohms secondary = 43.8 ohms primary
Check on ratio of resistive reach/Zone 1 forward ground loop reach
=
3.2
= 5.49
(0.56 /70
°
) x 1.04
The above ratio is within the limit of 15 (see Section 9)
19.9
Checking minimum relay voltage for a fault at the Zone 1 reach point
Maximum positive sequence impedance behind relay = 23.8 /76.4º ohms
Impedance to Zone 1 reach point = 4 /70
°
Overall source to fault impedance = (5.6 + j23.1) + (1.37 +j3.76)
= (6.97 + j26.9) = 27.8/75.5
°
Relay voltage for a phase fault at the Zone 1 reach point
= 4.0 x 110 = 15.8 volts
27.8
Maximum zero sequence impedance to the Zone 1 reach point is 16 /68
°
ohms
Source ground loop impedance
= 2 x (5.6 + j23.1) + (22.94 + j64.4)
3
= (11.34 + j36.87) = 38.6 /72.9
°
Summary of Contents for SHPM 101
Page 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Page 14: ......
Page 44: ......
Page 56: ......
Page 208: ......
Page 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Page 210: ......
Page 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Page 212: ......
Page 214: ......
Page 216: ......
Page 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Page 218: ......
Page 266: ......
Page 280: ......
Page 282: ......
Page 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Page 286: ......
Page 288: ......
Page 316: ......
Page 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Page 318: ......
Page 320: ......
Page 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Page 324: ......
Page 326: ......
Page 332: ......
Page 335: ......