Troubleshooting
P846/EN TS/D
MiCOM P846
(TS) 12-9
TS
7.3
Incorrect analog signals
The measurements may be configured in primary or secondary to assist. If it is suspected
that the analog quantities being measured by the relay are not correct then the measurement
function of the relay can be used to verify the nature of the problem. The measured values
displayed by the relay should be compared with the actual magnitudes at the relay terminals.
Verify that the correct terminals are being used (in particular the dual rated CT inputs) and
that the CT and VT ratios set on the relay are correct. The correct 120 degree displacement
of the phase measurements should be used to confirm that the inputs have been correctly
connected.
7.4
PSL editor troubleshooting
A failure to open a connection could be because of one or more of the following:
•
The relay address is not valid (note: this address is always 1 for the front port).
•
Password in not valid
•
Communication Set-up - COM port, Baud rate, or Framing - is not correct
•
Transaction values are not suitable for the relay and/or the type of connection
•
Modem configuration is not valid. Changes may be necessary when using a modem
•
The connection cable is not wired correctly or broken. See MiCOM S1 connection
configurations
•
The option switches on any KITZ101/102 this is in use may be incorrectly set
7.4.1
Diagram reconstruction after recover from relay
Although the extraction of a scheme from a relay is supported, the facility is provided as a
way of recovering a scheme in the event that the original file is unobtainable.
The recovered scheme will be logically correct, but much of the original graphical information
is lost. Many signals will be drawn in a vertical line down the left side of the canvas. Links
are drawn orthogonally using the shortest path from A to B.
Any annotation added to the original diagram (titles, notes, etc.) are lost.
Sometimes a gate type may not be what was expected, e.g. a 1-input AND gate in the
original scheme will appear as an OR gate when uploaded. Programmable gates with an
inputs-to-trigger value of 1 will also appear as OR gates.
7.4.2
PSL version check
The PSL is saved with a version reference, time stamp and CRC check. This gives a visual
check whether the default PSL is in place or whether a new application has been
downloaded.
Summary of Contents for MiCOM P846
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Page 6: ...P846 EN SS H11 Safety Section SS...
Page 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Page 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Page 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Page 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Page 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Page 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Page 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Page 78: ...P846 EN OP D Operation MiCOM P846 OP...
Page 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Page 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Page 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Page 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Page 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Page 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Page 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Page 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Page 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Page 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Page 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Page 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Page 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Page 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Page 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Page 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Page 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Page 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Page 282: ...P846 EN IN D Installation MiCOM P846 IN...
Page 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Page 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Page 297: ......